Plan Review Notes
Plan Review Notes For Permit 15110351
Permit Number 15110351
Review Stop B
Sequence Number 2
Notes
Date Text
2016-02-24 07:34:31PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO SECTION
 2413.6.1 OF THE 2014 FBC. THIS SECTION IS ONLY
 APPLICABLE TO STRUCTURES LOCATED IN THE HIGH VELOCITY
 HURRICANE ZONE ( DADE AND BROWARD COUNTIES ). THIS
 SECTION REQUIRES SHUTTERS USED TO PROTECT OPENINGS
 ABOVE THE FIRST FLOOR TO BE PERMANENTLY INSTALLED AND
 CLOSABLE FROM THE INSIDE OF THE BUILDING. THIS SECTION
 DOES NOT APPLY IN PALM BEACH COUNTY AND THE STORM
 PANELS YOU ARE USING DO NOT COMPLY. PLEASE REMOVE THIS
 NOTE FROM THE PLANS.
  
 2) SECTION 2411.3.1.6 THAT IS CITED IN THE GENERAL
 NOTES ON SEVERAL PLAN SHEETS ALSO DOES NOT APPLY
 OUTSIDE OF THE HIGH VELOCITY HURRICANE ZONE ( DADE AND
 BROWARD COUNTIES ).
  
 3) THE CORRECT SECTION FOR STRUCTURAL INDEPENDENCE OF
 THE ADJACENT UNIT IS FBC R302.2.4 AND NOT R317.2.4.
  
 4) FBC 1208.2 IS FROM THE 2014 FBC AND NOT THE
 FBC-RRESIDENTIAL. THE RESIDENTIAL CODE APPLIES TO
 TOWNHOUSES SUCH AS THIS PROJECT. THIS SECTION OF CODE
 IS LOCATED IN R305.1.
  
 5) FBC R302.11 IS THE SECTION FOR FIREBLOCKING AND NOT
 R4302.11. SEE SHEET D1.
  
 6) THE CORRECT SECTION FOR INSULATION FLAME SPREAD AND
 SMOKE DEVELOPED IS FBC R302.10.1.
  
 7) THE 2014 FBCR REFERENCES THE 2011 EDITIONS OF ACI
 530.1, ASCE 6-11 AND TMS 602. SEE CLOUDED AREA ON PLANS
 WHERE THE WRONG EDITIONS ARE CITED.
  
  
  
  