2016-02-23 18:59:58 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PLANS HAVE SEVERAL REFERENCES TO SECTION |
| 2413.6.1 OF THE 2014 FBC. THIS SECTION IS ONLY |
| APPLICABLE TO STRUCTURES LOCATED IN THE HIGH VELOCITY |
| HURRICANE ZONE ( DADE AND BROWARD COUNTIES ). THIS |
| SECTION REQUIRES SHUTTERS USED TO PROTECT OPENINGS |
| ABOVE THE FIRST FLOOR TO BE PERMANENTLY INSTALLED AND |
| CLOSABLE FROM THE INSIDE OF THE BUILDING. THIS SECTION |
| DOES NOT APPLY IN PALM BEACH COUNTY AND THE STORM |
| PANELS YOU ARE USING DO NOT COMPLY. PLEASE REMOVE THIS |
| NOTE FROM THE PLANS. |
| |
| 2) SECTION 2411.3.1.6 THAT IS CITED IN THE GENERAL |
| NOTES ON SEVERAL PLAN SHEETS ALSO DOES NOT APPLY |
| OUTSIDE OF THE HIGH VELOCITY HURRICANE ZONE ( DADE AND |
| BROWARD COUNTIES ). |
| |
| 3) THE CORRECT SECTION FOR STRUCTURAL INDEPENDENCE OF |
| THE ADJACENT UNIT IS FBC R302.2.4 AND NOT R317.2.4. |
| |
| 4) FBC 1208.2 IS FROM THE 2014 FBC AND NOT THE |
| FBC-RRESIDENTIAL. THE RESIDENTIAL CODE APPLIES TO |
| TOWNHOUSES SUCH AS THIS PROJECT. THIS SECTION OF CODE |
| IS LOCATED IN R305.1. |
| |
| 5) FBC R302.11 IS THE SECTION FOR FIREBLOCKING AND NOT |
| R4302.11. SEE SHEET D1. |
| |
| 6) THE CORRECT SECTION FOR INSULATION FLAME SPREAD AND |
| SMOKE DEVELOPED IS FBC R302.10.1. |
| |
| 7) THE 2014 FBCR REFERENCES THE 2011 EDITIONS OF ACI |
| 530.1, ASCE 6-11 AND TMS 602. SEE CLOUDED AREA ON PLANS |
| WHERE THE WRONG EDITIONS ARE CITED. |
| |
| |
| |
| |