2015-12-18 18:35:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION.
  
 2) THE ENERGY CALCULATION FORMS SPECIFY IECC ZONE 2.
 THE CITY OF WEST PALM IS IN PALM BEACH COUNTY WHICH IS
 IN CLIMATE ZONE 1A. FBC ENERGY CONSERVATION TABLE
 R301.1
  
 3) THE STORM PANEL SCHEDULES REFERENCE THE 2010 FBC.
 PLEASE CHANGE TO THE 2014 FBC.
  
 4) THE NOTES ON SECTION 2 SHEET D-1 AT THE PARTY WALL
 SHOULD REFERENCE 2014 FBC R302.2 AND NOT R317.2.
  
 5) THE CORRECT SECTION FOR STRUCTURAL INDEPENDENCE OF
 THE ADJACENT UNIT IS FBC R302.2.4 AND NOT R317.2.4.
  
 6) FBC R 4409.13.3.2.3 THAT IS SPECIFIED ON THE PLANS
 ONLY APPLIES TO THE HVHZ ( HIGH VELOCITY HURRICANE ZONE
 ) AND DOES NOT APPLY IN PALM BEACH COUNTY. THE CORRECT
 SECTION FOR THIS JURISDICTION IS FBC R 806.1 WHICH
 ALLOWS THE MAXIMUM SCREEN MESH OPENINGS TO BE 1/4 INCH.
  
 7) FBC R702.2.2 IS THE SECTION FOR MINIMUM STUCCO
 FINISH ON CONCRETE BLOCK AND NOT 4411.31.
  
 8) FBC R302.11 IS THE SECTION FOR FIREBLOCKING AND NOT
 R4409.7.1.
  
 9) THE CORRECT SECTION FOR INSULATION FLAME SPREAD AND
 SMOKE DEVELOPED IS FBC R302.10.1.
  
 10) FBC R302.2.2 IS THE SECTION THAT REQUIRES
 FIRE-RESISTANT PLYWOOD FOR 4 FEET ON EACH SIDE OF THE 2
 HOUR FIRE RATED PARTY WALL.
  
 11) THE 2014 FBCR REFERENCES THE 2011 EDITIONS OF ACI
 530.1, ASCE 6-11 AND TMS 602.
  
 12) THE ROOF SHEATHING FASTENING DETAIL DIAGRAM ON
 SHEET S-3 DOES NOT SHOW ROOF ZONE 3 FOR THE GABLE ROOF
 AREAS ON THE FRONT OF THE BUILDING. SEE FBC R803.2.3.1
  
 13) THE UPLIFT PRESSURES FOR THE ROOF COMPONENTS AND
 CLADDING ON SHEET S-6 ARE NOT CORRECT. ROOF ZONE 1 IS
 SPECIFIED AS -31.31 PSF AND ZONE 2 AND 3 ARE SPECIFIED
 AS -49.66 PSF. FBC-R 301.2.1
  
 14) THE ANCHOR SPACING IS BLANK ON THE STORM PANEL
 SCHEDULE FOR THE END A UNIT. FBC 107.2.1
  
 15) THE MAXIMUM NEGATIVE DESIGN PRESSURE LISTED IN THE
 PRODUCT APPROVAL FOR THE ENTRY DOOR IS -50 PSF. THE
 WIND PRESSURE FOR THE ENTRY DOOR IN THE EXTERIOR WALL
 ZONE IS SPECIFIED AS -55.08 PSF IN THE SCHEDULE ON THE
 PLANS. FBC-R301.1
  
 16) THE VALUATIONS FOR THE TOWNHOUSES ARE LOW BASED ON
 ICC VALUATION DATE AND WILL BE ADJUSTED AS FOLLOWS. THE
 1441 UNIT A IS $164,673.00. THE 1545 UNIT B IS
 $175,294.00. THE 1669 UNIT C IS $191,515.23.
  