Notes |
Date |
Text |
2015-11-10 12:07:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. APPLICATION IS TO INCLUDE THE FOLLOWING BASIC | | INFORMATION FOR REROOFS: MEAN ROOF HEIGHT, ROOF PITCH, | | DECK TYPE. | | | | 2. ON THE ROOF TILE PRODUCT APPROVAL, INDICATE METHOD | | OF FASTENING PROPOSED (DIRECT DECK AND DECK THICKNESS | | OR BATTENS, FASTENERS). THIS INFORMATION IS REQUIRED | | FOR RAS127 CALCULATIONS. THE CALCULATION WILL BE DONE | | FOR YOU BUT CANNOT BE DONE WITHOUT BASIC INFORMATION | | REGARDING THE INSTALLATION. | | | | 3. IF ADHESIVE IS PROPOSED FOR FASTENING, PROVIDE THE | | PRODUCT APPROVAL AND INDICATE PADDY SIZE PROPOSED. | | | | 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | 109. | | | | |
|