Plan Review Notes
Plan Review Notes For Permit 15110125
Permit Number 15110125
Review Stop B
Sequence Number 3
Notes
Date Text
2016-02-02 10:45:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110125
 ADD: 114 S. OLIVE AVE.
 CONT: HOOD DEPOT
 TEL: 954-570-9860
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: WED. DEC. 30/2015
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
 1) COMPLILED. WIND DESIGN CRITERIA ON THE PLANS.
  
  
 2A)(1) 3RD REQUEST. SEMI COMPLIED. PRECISION ALUMINUM
 PRODUCTS/ A/C STANDS SUBMITTED ENGINEERING FROM FRANK
 BENNARDO NO COVERE SHEETS WERE PROVIDED INDICATING THIS
 IS A FLORIDA APPROVAL OR A MIAMI-DADE NOA.
  
 2A)(2) SHEET 3 OF 7 SHOWS 3 ROOF TOP CONDENING UNITS
 AND ROOF TOP STAND AND ROOF TOP CURBS INTAKE AND
 EXHAUST FANS PLEASE PROVIDE EITHER A FLORIDA APPROVAL
 OR MIAMI-DADE NOA. . PLEASE SHOW COMPLIANCE WITH:
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOF TOP CURBS, ROOF TOP INTAKE & EXHAUST FANS
 -NO PRODUCT APPROVALS WERE SUBMITTED!!!!
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 2B) 3RD REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) 3RD REQUEST.THE ENGINEER OF RECORD (STRUCTURAL) HAS
 NOT REVIEWED THESE PLANS FOR CODE COMPLIANCE, NOR
 AFFIXED THERE SHOP DRAWING STAMPED REVIEWED AND
 APPROVED. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  