Date |
Text |
2016-01-14 14:42:43 | YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED |
| DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL |
| REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED |
| BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO |
| SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE |
| REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION |
| OF ANY PREVIOUS COMMENTS. |
| |
| 1. THIS TIME THE MASTER PERMIT REFERRED TO ON THE |
| APPLICATION IS FOR THE COMMERCIAL REMODEL OF THE BLDG. |
| BUT THE KITCHEN HOOD SYSTEM SPECIFIED ON THE MASTER |
| PERMIT DIFFERS FROM THE ONE BEING PROPOSED ON THIS |
| APPLICATION THEREFORE ALL ELECTRICAL REQUIREMENTS AS |
| PREVIOUSLY REQUESTED SHALL BE SUBMITTED FOR REVIEW. |
| 2. THE SYSTEM ON THE MASTER PERMIT IS A CAPTIVE AIR AND |
| THIS IS A HOOD DEPOT. |
| 3. YOU SHALL PROVIDE CIRCUIT DIRECTORY, WIRING DIAGRAM |
| AND LOAD CALCS FOR BOTH, THE HOOD FAN MOTORS AND THE |
| MUA COOLING SYSTEM. |
| 4. PROVIDE SHUNT TRIP BREAKER FOR ALL ELECTRICAL |
| EQUIPMENT AND OUTLETS UNDER THE HOOD. |
| 5. YOU SHALL PROVIDE A CORRECTED CIRCUIT DIRECTORY FOR |
| THE PANELS AFFECTED BY THIS MODIFICATION. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE?SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE?SUBMITTAL FORM, AS WELL AS AN |
| INDICATION ON THE PAGE WHERE THE CORRECTION WAS |
| PERFORMED. ADDITIONALLY, PLEASE INSERT CORRECTED PAGES |
| INTO THE SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARISON. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. IF YOU HAVE FURTHER QUESTIONS, |
| PLEASE DON?T HESITATE TO CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH.: 561?805?6746 |
| EMAIL: [email protected] |
| |