2016-01-14 14:42:43YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
  
 1. THIS TIME THE MASTER PERMIT REFERRED TO ON THE
 APPLICATION IS FOR THE COMMERCIAL REMODEL OF THE BLDG.
 BUT THE KITCHEN HOOD SYSTEM SPECIFIED ON THE MASTER
 PERMIT DIFFERS FROM THE ONE BEING PROPOSED ON THIS
 APPLICATION THEREFORE ALL ELECTRICAL REQUIREMENTS AS
 PREVIOUSLY REQUESTED SHALL BE SUBMITTED FOR REVIEW.
 2. THE SYSTEM ON THE MASTER PERMIT IS A CAPTIVE AIR AND
 THIS IS A HOOD DEPOT.
 3. YOU SHALL PROVIDE CIRCUIT DIRECTORY, WIRING DIAGRAM
 AND LOAD CALCS FOR BOTH, THE HOOD FAN MOTORS AND THE
 MUA COOLING SYSTEM.
 4. PROVIDE SHUNT TRIP BREAKER FOR ALL ELECTRICAL
 EQUIPMENT AND OUTLETS UNDER THE HOOD.
 5. YOU SHALL PROVIDE A CORRECTED CIRCUIT DIRECTORY FOR
 THE PANELS AFFECTED BY THIS MODIFICATION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE?SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE?SUBMITTAL FORM, AS WELL AS AN
 INDICATION ON THE PAGE WHERE THE CORRECTION WAS
 PERFORMED. ADDITIONALLY, PLEASE INSERT CORRECTED PAGES
 INTO THE SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARISON. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED. IF YOU HAVE FURTHER QUESTIONS,
 PLEASE DON?T HESITATE TO CONTACT ME DIRECTLY.
  