2015-12-09 10:04:29 | 1ST REVIEW 2014 MECHANICAL |
| PERMIT #15110125 |
| 12/9/15 |
| |
| 1) THE HOOD 1A & 1B SUPPLY FAN AIR INLET (SF-1) SHALL |
| NOT BE LOCATED IN AN ALLEY, AND NOT WITHIN THE REQUIRED |
| 10' CLEARANCE DISTANCE TO THE ADJACENT PROPERTY LINE- |
| REFER TO SECTIONS 508.1 AND 401.4 FBC-14 MECHANICAL. |
| 2) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR |
| ALL EXTERIOR FAN AND DUCT INSTALLATIONS, INCLUDING THE |
| SUPPORT PLATFORMS AND BRACKET ASSEMBLIES IN THE ALLEY- |
| SEE SECTION 301.5 AND PROVIDE THE WIND LOAD DESIGN |
| CRITERIA ON THE PLANS AND COMPLETE DETAILS. PLEASE |
| NOTE: A) SHOP DRAWINGS FOR ALL THE STRUCTURAL |
| ASSEMBLIES SHALL BE REVIEWED AND APPROVED BY THE |
| ENGINEER OF RECORD AND SUBMITTED TO THE BUILDING |
| DEPARTMENT. B)WELDING CERTIFICATIONS SHALL BE ON-SITE |
| AT TIME OF INSPECTION. |
| 3) PROVIDE UL TESTED AND APPROVED FIRE STOPPING |
| ASSEMBLIES ON THE PLAN FOR THE DUCTS PENETRATING THE |
| FIRE-RATED EXTERIOR WALL. |
| 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| OF ALL APPLIANCES AND EQUIPMENT AND THE MINIMUM |
| REQUIRED CLEARANCE DISTANCES FOR EXHAUST AND VENT |
| OUTLETS, AND MECHANICAL AND GRAVITY AIR INTAKES- REFER |
| TO SECTIONS 401.4, 501.3.1, AND 506.3.1. PLEASE NOTE A |
| REVISION TO THE ORIGINAL MECHANICAL ROOF PLAN SHEET |
| SUBMITTED UNDER THE PERMIT # 13060638 MAY BE REQUIRED |
| FOR REVIEW AND FOR PUBLIC RECORD. SEE ALSO SECTION |
| 304.11: GUARDS MAY BE REQUIRED FOR EQUIPMENT WITHIN 10' |
| OF A ROOF EDGE. |
| 5) PROVIDE AIR VELOCITY CALCULATIONS FOR THE EXHAUST |
| DUCTS- SECTION 506.3.4. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |
| |