2015-12-09 10:04:291ST REVIEW 2014 MECHANICAL
 PERMIT #15110125
 12/9/15
  
 1) THE HOOD 1A & 1B SUPPLY FAN AIR INLET (SF-1) SHALL
 NOT BE LOCATED IN AN ALLEY, AND NOT WITHIN THE REQUIRED
 10' CLEARANCE DISTANCE TO THE ADJACENT PROPERTY LINE-
 REFER TO SECTIONS 508.1 AND 401.4 FBC-14 MECHANICAL.
 2) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 ALL EXTERIOR FAN AND DUCT INSTALLATIONS, INCLUDING THE
 SUPPORT PLATFORMS AND BRACKET ASSEMBLIES IN THE ALLEY-
 SEE SECTION 301.5 AND PROVIDE THE WIND LOAD DESIGN
 CRITERIA ON THE PLANS AND COMPLETE DETAILS. PLEASE
 NOTE: A) SHOP DRAWINGS FOR ALL THE STRUCTURAL
 ASSEMBLIES SHALL BE REVIEWED AND APPROVED BY THE
 ENGINEER OF RECORD AND SUBMITTED TO THE BUILDING
 DEPARTMENT. B)WELDING CERTIFICATIONS SHALL BE ON-SITE
 AT TIME OF INSPECTION.
 3) PROVIDE UL TESTED AND APPROVED FIRE STOPPING
 ASSEMBLIES ON THE PLAN FOR THE DUCTS PENETRATING THE
 FIRE-RATED EXTERIOR WALL.
 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL APPLIANCES AND EQUIPMENT AND THE MINIMUM
 REQUIRED CLEARANCE DISTANCES FOR EXHAUST AND VENT
 OUTLETS, AND MECHANICAL AND GRAVITY AIR INTAKES- REFER
 TO SECTIONS 401.4, 501.3.1, AND 506.3.1. PLEASE NOTE A
 REVISION TO THE ORIGINAL MECHANICAL ROOF PLAN SHEET
 SUBMITTED UNDER THE PERMIT # 13060638 MAY BE REQUIRED
 FOR REVIEW AND FOR PUBLIC RECORD. SEE ALSO SECTION
 304.11: GUARDS MAY BE REQUIRED FOR EQUIPMENT WITHIN 10'
 OF A ROOF EDGE.
 5) PROVIDE AIR VELOCITY CALCULATIONS FOR THE EXHAUST
 DUCTS- SECTION 506.3.4.
  