Plan Review Notes For Permit 15110125 |
Permit Number |
15110125 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-11-16 12:05:32 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. PLEASE PROVIDE GREATER DETAIL OF THE LOCATION OF THE | | HOOD SYSTEM AS IT APPEARS TO BE IN AN ALLEY. | | | | 2. THE HEIGHT OF THE CLEARENCE FROM THE GROUND, WITHIN | | THE ALLEY, SHALL BE A MINIMUM OF 13'6". | | | | 3. THE LOCATION OF THE 2ND HOOD EXHAUST APPEARS TO BE | | TOO CLOSE TO THE ROOF A/C. PROVIDE GREATER DETAIL. | | | | 4. PROVIDE A FIRE RATED LISTING FOR PENETRATING THE | | EXTERIOR WALL. |
|