Plan Review Notes
Plan Review Notes For Permit 15110125
Permit Number 15110125
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-11-16 12:05:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE GREATER DETAIL OF THE LOCATION OF THE
 HOOD SYSTEM AS IT APPEARS TO BE IN AN ALLEY.
  
 2. THE HEIGHT OF THE CLEARENCE FROM THE GROUND, WITHIN
 THE ALLEY, SHALL BE A MINIMUM OF 13'6".
  
 3. THE LOCATION OF THE 2ND HOOD EXHAUST APPEARS TO BE
 TOO CLOSE TO THE ROOF A/C. PROVIDE GREATER DETAIL.
  
 4. PROVIDE A FIRE RATED LISTING FOR PENETRATING THE
 EXTERIOR WALL.