Plan Review Notes
Plan Review Notes For Permit 15110125
Permit Number 15110125
Review Stop E
Sequence Number 1
Notes
Date Text
2015-12-11 10:54:16THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE MASTER PERMIT REFERRED TO ON THIS APPLICATION IS
 FOR A FIRE SPRINKLER SYSTEM AND HAS NOTHING TO DO WITH
 THE INSTALLATION OF KITCHEN HOODS. THEREFORE A COMPLETE
 ELECTRICAL DRAWING SHALL BE PROVIDED.
 2. THE FAN SCHEDULE AND CONTROL PANEL INPUT VOLTAGES DO
 NOT MATCH ON THE SUBMITTED DRAWINGS. REVISE DRAWINGS TO
 ADDRESS THIS ISSUE.
 3. YOU SHALL PROVIDE CIRCUIT DIRECTORY, WIRING DIAGRAM
 AND LOAD CALCS FOR THIS ADDED LOAD.
 4. PROVIDE SHUNT TRIP BREAKER FOR ALL ELECTRICAL
 EQUIPMENT AND OUTLETS UNDER THE HOOD.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  