2015-12-14 13:55:39 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15110125 |
| ADD: 114 S. OLIVE AVE. |
| CONT: HOOD DEPOT |
| TEL: 954-570-9860 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| 1ST REVIEW |
| DATE: MON. DEC. 21/2015 |
| ACTION: DENIED |
| |
| 1) THE (7) MECHANICAL SHEETS SUBMITTED BY HOOD DEPOT DO |
| NOT HAVE THE WIND DESIGN CRITERIA ON THE PLANS, |
| |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 1.2. RISK CATEGORY. |
| |
| 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 2A) SHEET 3 OF 7 SHOWS 3 ROOF TOP CONDENING UNITS AND |
| ROOF TOP STAND. PLEASE SHOW COMPLIANCE WITH: FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31 (G) PRE-ENGINEERED A/C STANDS |
| |
| 2B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 3) SHEET 5OF 7 SHOWS THE AIR COMPRESSOR BEING HUNG FROM |
| THE SIDE OF THE THRESHOLD BUILDING. ALL THRESHOLD |
| INSPECTIONS ARE TO BE PREFORMED BY THE THRESHOLD |
| INSPECTOR. THE SECOND ISSUE IS THE ENGINEER OF RECORD |
| HAS NOT REVIEWED THESE PLANS FOR CODE COMPLIANCE, NOR |
| AFFIXED THERE SHOP DRAWING STAMPED REVIEWED AND |
| APPROVED. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| THE ENGINEER OF RECORD FOR REVIEW. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |