2015-12-14 13:55:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110125
 ADD: 114 S. OLIVE AVE.
 CONT: HOOD DEPOT
 TEL: 954-570-9860
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: MON. DEC. 21/2015
 ACTION: DENIED
  
 1) THE (7) MECHANICAL SHEETS SUBMITTED BY HOOD DEPOT DO
 NOT HAVE THE WIND DESIGN CRITERIA ON THE PLANS,
  
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2A) SHEET 3 OF 7 SHOWS 3 ROOF TOP CONDENING UNITS AND
 ROOF TOP STAND. PLEASE SHOW COMPLIANCE WITH: FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31 (G) PRE-ENGINEERED A/C STANDS
  
 2B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 3) SHEET 5OF 7 SHOWS THE AIR COMPRESSOR BEING HUNG FROM
 THE SIDE OF THE THRESHOLD BUILDING. ALL THRESHOLD
 INSPECTIONS ARE TO BE PREFORMED BY THE THRESHOLD
 INSPECTOR. THE SECOND ISSUE IS THE ENGINEER OF RECORD
 HAS NOT REVIEWED THESE PLANS FOR CODE COMPLIANCE, NOR
 AFFIXED THERE SHOP DRAWING STAMPED REVIEWED AND
 APPROVED. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER