2015-11-05 12:46:42THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. THESE DRAWINGS BEING THAT THEY ARE FOR THE ACTUAL
 INSTALLATION OF THE HOOD SYSTEM AND THE ASSOCIATED FAN
 MOTORS WILL REQUIRE IN ADDITION TO THE A SITE SPECIFIC
 WIRING DIAGRAM YOU WILL HAVE TO SUBMIT SPECS FOR BOTH,
 THE EXHAUST AND MAKE UP AIR BLOWER MOTORS.
 2. YOU WILL PROVIDE A CIRCUIT DIRECTORY OF THE PANEL
 WHERE THESE MOTORS ARE BEING SERVED FROM.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  