Plan Review Notes
Plan Review Notes For Permit 15101016
Permit Number 15101016
Review Stop G
Sequence Number 1
Notes
Date Text
2015-11-02 09:17:261) SUBMIT A GAS PIPING RISER FOR REVIEW. SHOW THE TYPE
 OF PIPE MATERIAL, THE TOTAL BTU LOAD ON THE SYSTEM, THE
 DISTANCE OF THE MOST REMOTE OUTLET FROM THE SOURCE TO
 THE MOST REMOTE OUTLET AND THE PIPE SIZE. INDICATE THE
 SPECIFIC SIZING TABLE FROM THE CODE THAT THE SYSTEM IS
 BASED ON. WPB AMEND. TO FBC SEC. 107.
 2) INDICATE THE LOCATION OF THE GAS PIPING ON THE PLAN.
 IS THIS NEW GAS PIPING OR IS THE DRYER CONNECTING TO AN
 EXISTING OUTLET? IS THE DRYER BEING RELOCATED OR IS
 THIS AN ADDITIONAL GAS LOAD ON AN EXISTING SYSTEM ?
 SHOW WHAT IS NEW AND EXISTING. CLARIFY.
 3) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR THE GAS
 APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED PER
 THE 2014 FBC SER. G2404.3.
 4) SUBMIT DETAILS / CALCULATIONS FOR COMBUSTION AIR FOR
 THE GAS DRYER PER THE 2014 FBC-RESIDENTIAL SEC. G2407.
 5) SUBMIT DETAILS FOR THE GAS DRYER EXHAUST.CLOTHES
 DRYER EXHAUST SHALL CCOMPLY WITH THE 2014 FBC-
 RESIDENTIAL SEC. G2439. UNITS EXHAUSTING MORE THAN 200
 CFM SHALL BE PROVIDED WITH MAKEUP AIR PER SEC.
 G2439.4.SUBMIT THE INSTALLATION MANUAL FOR REVIEW.
 6) INDICATE THE TYPE OF GAS (NATURAL OR LP).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  