Plan Review Notes For Permit 15100827 |
Permit Number |
15100827 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-11-10 08:01:30 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #15100827 | | 11/10/16 | | | | 1) THE CODE SUMMARY ON THE COVER SHEET MP-101 INDICATES | | THE 1ST AND 2ND LEVELS OF THE GARAGE ARE ENCLOSED. | | REFER TO SHEET MP-101 AND REVISE THE PLAN TO SHOW THE | | REQUIRED EXHAUST SYSTEM ON LEVEL 2 PER SECTION 404.1. | | | | 2) REFER TO TABLE 403.3 AND SECTION 404.2 AND PROVIDE | | EXHAUST VENTILATION CALCULATIONS ON THE PLAN FOR LEVELS | | 1 & 2. | | | | 3) 3RD REQUEST FOR AC COOLING AND HEATING CALCULATIONS | | FOR THE MINI-SPLIT SYSTEMS, 3RD REQUEST TO REMOVE THE | | MAIN COURTHOUSE ENERGY CALCS FROM THE FILE AND REPLACE | | WITH CALCS FOR THE GARAGE. | | | | 4) 3RD REQUEST FOR: A) CONDENSATE DISPOSAL PLAN. B) | | NOA'S FOR THE LOUVERS. C) SPECS FOR THE CO AND NO2 | | DETECTORS. | | | | 5) TO HELP EXPEDITE THE REVIEW [PROCESS AND APPROVAL OF | | THE PLANS, PLEASE PROVIDE A RESPONSE NARRATIVE RESPONSE | | TO THESE COMMENTS FROM THE DESIGN PROFESSIONAL. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|