2016-11-10 08:01:303RD REVIEW FBC-2014 MECHANICAL
 PERMIT #15100827
 11/10/16
  
 1) THE CODE SUMMARY ON THE COVER SHEET MP-101 INDICATES
 THE 1ST AND 2ND LEVELS OF THE GARAGE ARE ENCLOSED.
 REFER TO SHEET MP-101 AND REVISE THE PLAN TO SHOW THE
 REQUIRED EXHAUST SYSTEM ON LEVEL 2 PER SECTION 404.1.
  
 2) REFER TO TABLE 403.3 AND SECTION 404.2 AND PROVIDE
 EXHAUST VENTILATION CALCULATIONS ON THE PLAN FOR LEVELS
 1 & 2.
  
 3) 3RD REQUEST FOR AC COOLING AND HEATING CALCULATIONS
 FOR THE MINI-SPLIT SYSTEMS, 3RD REQUEST TO REMOVE THE
 MAIN COURTHOUSE ENERGY CALCS FROM THE FILE AND REPLACE
 WITH CALCS FOR THE GARAGE.
  
 4) 3RD REQUEST FOR: A) CONDENSATE DISPOSAL PLAN. B)
 NOA'S FOR THE LOUVERS. C) SPECS FOR THE CO AND NO2
 DETECTORS.
  
 5) TO HELP EXPEDITE THE REVIEW [PROCESS AND APPROVAL OF
 THE PLANS, PLEASE PROVIDE A RESPONSE NARRATIVE RESPONSE
 TO THESE COMMENTS FROM THE DESIGN PROFESSIONAL.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  