2016-05-05 17:30:54 | 2ND REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15100827 |
| 5/5/16 |
| |
| SOME OF THE COMMENTS FROM THE 1ST REVIEW STILL EXIST |
| AND SOME NEW ISSUES REGARDING THE RE-SUBMITTED PLANS |
| HAVE COME ABOUT. |
| |
| 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE THE FOLLOWING |
| ITEMS: A) AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW MINI-SPLIT SYSTEMS. B) WIND LOAD ENGINEERING FOR |
| THE CONDENSER ON THE 2ND FLOOR C) CONDENSATE DISPOSAL |
| FOR THE NEW AIR HANDLERS. D) ENERGY CALCULATIONS |
| (PLEASE NOTE THE SUBMITTED ENERGY CALCULATIONS ARE FOR |
| THE MAIN COURTHOUSE BUILDING). |
| 2) SHEET MP-101: PLEASE CORRECT NOTE #3 TO READ "SHALL |
| NOT OPERATE BELOW MINIMUM FLOW OF 1700 CFM......." |
| 3) PROVIDE OPENING PROTECTION FOR EF-G-1 AND EF-G-2 IN |
| COMPLIANCE WITH SECTION 501.3.2 FBC-14 MECHANICAL. |
| 4) INDICATE THE CLEARANCE HEIGHT FROM THE FINISHED |
| FLOOR TO THE BOTTOM EDGES OF THE EXHAUST FANS, AIR |
| HANDLERS, AND ALL OTHER MECHANICAL EQUIPMENT LOCATED IN |
| THE GARAGES- SEE SECTION 304.3. |
| 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE CO AND NO2 DETECTORS |
| WITH APPROVAL SIGNATURE BY THE ENGINEER OF RECORD. |
| 6) SUBMIT A FLORIDA PRODUCT APPROVAL AND/OR A |
| MIAMI-DADE NOA FOR THE LOUVERS. |
| 7) REFER TO SECTIONS 401.4 AND 501.3.1 AND INDICATE |
| WITH NOTES OR DETAILS THE REQUIRED CLEARANCE DISTANCE |
| MEASUREMENTS FOR THE AIR INTAKES AND EXHAUST OUITLETS. |
| |