2016-05-05 17:30:542ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100827
 5/5/16
  
 SOME OF THE COMMENTS FROM THE 1ST REVIEW STILL EXIST
 AND SOME NEW ISSUES REGARDING THE RE-SUBMITTED PLANS
 HAVE COME ABOUT.
  
 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE THE FOLLOWING
 ITEMS: A) AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MINI-SPLIT SYSTEMS. B) WIND LOAD ENGINEERING FOR
 THE CONDENSER ON THE 2ND FLOOR C) CONDENSATE DISPOSAL
 FOR THE NEW AIR HANDLERS. D) ENERGY CALCULATIONS
 (PLEASE NOTE THE SUBMITTED ENERGY CALCULATIONS ARE FOR
 THE MAIN COURTHOUSE BUILDING).
 2) SHEET MP-101: PLEASE CORRECT NOTE #3 TO READ "SHALL
 NOT OPERATE BELOW MINIMUM FLOW OF 1700 CFM......."
 3) PROVIDE OPENING PROTECTION FOR EF-G-1 AND EF-G-2 IN
 COMPLIANCE WITH SECTION 501.3.2 FBC-14 MECHANICAL.
 4) INDICATE THE CLEARANCE HEIGHT FROM THE FINISHED
 FLOOR TO THE BOTTOM EDGES OF THE EXHAUST FANS, AIR
 HANDLERS, AND ALL OTHER MECHANICAL EQUIPMENT LOCATED IN
 THE GARAGES- SEE SECTION 304.3.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE CO AND NO2 DETECTORS
 WITH APPROVAL SIGNATURE BY THE ENGINEER OF RECORD.
 6) SUBMIT A FLORIDA PRODUCT APPROVAL AND/OR A
 MIAMI-DADE NOA FOR THE LOUVERS.
 7) REFER TO SECTIONS 401.4 AND 501.3.1 AND INDICATE
 WITH NOTES OR DETAILS THE REQUIRED CLEARANCE DISTANCE
 MEASUREMENTS FOR THE AIR INTAKES AND EXHAUST OUITLETS.
  