2016-05-12 16:58:46 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15100827 |
| ADD: 111 S. SAPODILLA AVE. |
| CONT: THE WEITZ CO. |
| TEL: (561)686-5511 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: THURS. MAY 12/2016 |
| ACTION: DENIED |
| |
| 1) SHEET G.01/ COVERSHEET: |
| |
| 1A-D) COMPLIED |
| |
| 1E) 2ND REQUEST. SHEET G.01/ COVERSHEET NOR SHEET A100 |
| THE SITE PLAN SHOW AN ASSUMED PROPERTY LINE TO THE EAST |
| OR WEST OF THE BUILDING FOR FIRE RESISTANCE RATING |
| REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| SEPARATION FBC-B TABLE 601 & ALLOWABLE OPENINGS FOR |
| UNPROTECTED, NON-SPRINKLERED BUILDINGS FBC-B TABLE |
| 705.8 . |
| 406.5.6 FIRE SEPARATION DISTANCE. EXTERIOR WALLS AND |
| OPENINGS IN EXTERIOR WALLS SHALL COMPLY WITH TABLES 601 |
| AND 602. THE DISTANCE TO AN ADJACENT LOT LINE SHALL BE |
| DETERMINED IN ACCORDANCE WITH TABLE 602 AND SECTION |
| 705. |
| |
| 2) THIS BUILDING IS A 4 STORY/ 4 TIER BUILDING. |
| THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| 2B) COMPLIED. THRESHOLD INSPECTION FORMS. |
| |
| 2C)COMPLIED. FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| OR HIS DESIGNEE WILL REVIEW THE RESUME'. |
| |
| 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION |
| |
| 2F) COMPLIED. 3 SETS OF DOCUMENTS. |
| |
| 2G) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM |
| BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF |
| JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN |
| 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| 2H) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| PENETRATIONS, FOR WALLS AND CEILINGS. |
| |
| 3) COMPLIED. 2014 FBC-B 406.5.8 STANDPIPE SYSTEM |
| |
| 4-6) COMPLIED |
| |
| 7) 2ND REQUEST. RESPONSE INDICATES SEE SHEET S.002 |
| SPECS 13-31-36 FOR FABRIC AWNINGS. THE HEADING 13-31 |
| (1) (A-F) ARE REQUIRED SHOP DRAWINGS, FABRIC AWNINGS |
| WERE NOT INCLUDED IN THIS LIST. |
| SHEET AP.46 DETAIL # 2,3 & 4 SHOWS AWNINGS, THERE IS NO |
| DETAIL AS TO MATERIAL AND OR FRAMEWORK FOR THE AWNINGS |
| NOR WIND DESIGN CRITERIA? 2014 FBC-B FABRIC AWNINGS IN |
| COMPLIANCE WITH 3105.4 OR RIGID AWNINGS IN COMPLIANCE |
| WITH 3105.5? |
| |
| 8) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2010 FBC-B |
| 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. SWING & OVERHEAD GARAGE DOOR. |
| (C) WALL LOUVERS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 9) BUILDING PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |