Plan Review Notes
Plan Review Notes For Permit 15100827
Permit Number 15100827
Review Stop P
Sequence Number 1
Notes
Date Text
2015-11-03 15:27:001) SUBMIT A STORM DRAINAGE RISER DIAGRAM AND AN
 OVERFLOW DRAINAGE RISER DIAGRAM FOR REVIEW. SHOW THE
 SQUARE FOOT AREA DRAINED BY EACH DRAIN. HORIZONTAL
 STORM DRAIN PIPING SHALL BE SIZED IN ACCORDANCE WITH
 2014 FBC-PLUMBING TABLE 1106.3 AND THE VERTICAL
 CONDUCTORS & LEADERS SHALL BE SIZED IN ACCORDANCE WITH
 TABLE 1106.2 (1). INCLUDE 1/2 THE AREA OF ANY VERTICAL
 THAT DIVERTS RAINWATER TO THE ROOF IN THE SQUARE
 FOOTAGE CALCULATIONS. THE RAINFALL RATE TO BE USED IS 5
 INCHES FOR THE DESIGN.WPB AMEND. TO FBC 107.3.5.1.3.
 2) INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAIN
 PIPING ON THE PLAN. COMPLY WITH TABLE 1106.3 FOR SLOPE
 AND SIZING REQS.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE STANCOR SYSTEM FOR THE ELEVATOR
 SUMP.WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT A SANITARY RISERR DIAGRAM FOR THE PIPING/PUMP
 FOR THE ELEVATOR SUMP. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 5) INDICATE ON THE PLAN IF THE 3 INCH PVC FORCE MAIN
 WILL BE RUN IN ITS ENTIRETY FROM THE PARKING GARAGE TO
 THE MANHOLE LOCATED IN PHASE II UNDER THIS PERMIT.
 6) PROVIDE OVERFLOW DRAINS/SCUPPERS FOR THE 4TH LEVEL
 PARKING AREA WHERE THE ROOF DRAINS ARE LOCATED IN
 ACCORDANCE WITH 2014 FBC-PLUMBING SEC.1108.
  
 PLUMBING PLAN REVIEW