2015-11-04 15:35:541ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100827
 11/4/2015
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 DUCTLESS SPLIT SYSTEMS IN THE 1ST FLOOR ELECTRIC ROOM,
 AND THE 4TH FLOOR ELEVATOR MACHINE ROOM- SEE SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
 2) SHEET MP-101 & MP-102: INDICATE HOW THE 2ND AND 3RD
 FLOOR UNIDENTIFIED ROOMS ADJACENT TO THE ELEVATOR ARE
 BEING VENTILATED. THE DRAWINGS INDICATE DOORWAYS AND
 SOME TYPE OF EQUIPMENT IN THE ROOMS WHICH IS ALSO
 UNIDENTIFIED: PLEASE CLARIFY.
 3) ENERGY CALCULATIONS ARE REQUIRED PER SECTION C101.2
 FBC-14 ENERGY CONSERVATION. SEE SECTION C101.5 AND
 SUBMIT THE COMPLIANCE DOCUMENTS.
 4) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 THE CONDENSERS INSTALLED IN THE OPEN GARAGE IN
 COMPLIANCE WITH SECTION 301,15. THE ENGINEER OF RECORD
 SHALL PROVIDE THE WIND LOAD DESIGN CRITERIA, DESIGN
 PRESSURES, AND DRAWINGS AND DETAILS FOR COMPLETE
 INSTALLATIONS.
 5) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE TWO AIR
 HANDLERS.
  