2015-10-30 15:22:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1. SHEET AP .00, INDICATES UNPROTECTED AND UNSECURED |
| AREAS AREAS OF EXIT BY THE STARIWAY EXITS AND |
| ELEVATORS. NFPA 101 CHAPTER 7, MEANS OF EGRESS, 7.1.10 |
| MEANS OF EGRESS RELIABILITY, 7.1.10.1 GENERAL. MEANS OF |
| EGRESS SHALL BE CONTINUOUSLY MAINTAINED FREE OF ALL |
| OBSTRUCTION OR IMPEDIMENTS TO FULL INSTANT USE IN THE |
| CASE OF FIRE OR OTHER EMERGENCY. THESE AREAS SHALL BE |
| PROTECTED AGASIT VEHICLE TRAFFIC AND VEHICLE PARKING; |
| ADDITIONALLY, FROM PEDSTRIAN GATHERING AT THE ELEVATOR |
| AND STAIRWAYS, AS WELL AS, FIREFIGHTER OPERATIONS FROM |
| THE STAIRWELL STANDPIPE OPERATIONS. THOSE AREAS SHALL |
| BE PROTECTED BY 4' BOLLARDS AT 36" INCHES HIGH, 48" ON |
| CENTER WITH REFELCTIVE MARKINGS. |
| |
| |
| 2. SHEET G.01, OR OTHER REFERENCE PAGE HAS NO |
| INDICATION OF ELEVATOR SERVICE, NFPA 11.3 ELEVATORS, |
| ESCALATORS, AND CONVEYORS, 11.3.1 FIRE FIGHTERS |
| EMERGENCY OPERATIONS, 11.3.1.1 ALL NEW ELEVATORS SHALL |
| CONFORM TO THE FIRE FIGHTERS EMERGCNEY OPERATIONS |
| REQUIRMENTS OF ASME A17.1/CSA B44, SAFETY CODE FOR |
| ELEVATORS AND ESCALATORS. |
| |
| 3. SHEET G.01, OR OTHER REFERENCE PAGE HAS NO |
| INDICATION. ALL LIFE SAFETY SYSTEMS WORK SHALL BE DONE |
| THROUGH SEPARATE SHOP DRAWINGS BY A CERTIFIED LIFE |
| SAFETY CONTRACTOR. |
| |
| 4. SHEET EP- 101, EXIT SIGN LOCATIONS ARE NOT CLEARLY |
| INDICATING THAT THEY CAN BE VISIBLE FORM ALL LOCATIONS |
| ON EACH FLOOR. EXIT SIGNS SHALL BE LOCATED PER NFPA |
| 101, CHAPTER 7, 7.10 MARKING OF MEANS OF EGRESS, |
| INCLUDING VISIBILITY, FLOOR PROXIMITY, MOUNTING, |
| DIRECTIONAL, TACTILE. |
| |
| 5. SHEET AP 52 - 53, EXIT STAIR LANDINGS GUARDS AND |
| HANDRAILS SHALL BE MARKED PER NFPA 101, CHAPTER 7, |
| 7.2.2.5.5 THROUGH 7.2.2.5.5.3 . |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |