Plan Review Notes
Plan Review Notes For Permit 15100827
Permit Number 15100827
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-05 14:24:25THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE APPLICABLE NEC (NFPA 70) FOR THIS JOB IS THE
 2011 EDITION. CORRECT SHEET G01 ACCORDINGLY.
 2. YOU ARE IN ESSENCE PARALLELING THE GROUNDED
 CONDUCTOR WITH THE ADDITION OF THE #4 IN THE SERVICE
 RACEWAY IN VIOLATION OF THE REQUIREMENTS STATED IN NEC
 310.10(H)(2).
 3. ACCORDING TO NEC 250.66 THE MINIMUM GROUNDING
 ELECTRODE CONDUCTOR FOR THE 4/0 SERVICE CONDUCTORS IS A
 #2, NOT EVEN THE #4 INDICATED.
 4. PANEL GLP CKT 1 FACP SHALL COMPLY W/NEC 760.41(B).
 5. THE FACP IN THE ELECTRICAL ROOM APPEARS TO BE
 SELF-SUPPORTING IN THE CENTER OF THE ROOM. CORRECT AS
 REQUIRED.
 6. INSTALL THE REQUIRED EXIT LIGHTING AS INDICATED BY
 FBC-B SECTION 1011.
 7. THE WIND LOAD RATING FOR THE LIGHTING POLES ON THE
 TOP FLOOR SHALL BE 170 MPH.
 8. ALL FIRE ALARM WORK SHALL BE UNDER A SEPARATE PERMIT
 AND SUBMITTAL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
  