2015-11-13 14:28:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100827
 ADD: 111 S. SAPODILLA AVE.
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
  
 1ST REVIEW
 DATE: FRI. NOV. 13/2015
 ACTION: DENIED
  
 1) SHEET G.01/ COVERSHEET:
  
 1A) THE CITY ADDRESSING RECORDS AS WELL AS PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE FOR PCN:
 74-43-43-21-30-001-0000 LISTS THIS SITE ADDRESS AS 111
 S. SAPODILLA AVE. PLEASE CORRECT THE ADDRESS ON ALL THE
 PLANS.
  
 1B) CONSTRUCTION TYPE: LISTED AS A TYPE II-B BUILDING
 OPEN
  
 1B)(1) THE PLANS DO NOT INDICATE HOW MANY SQ. FT. ARE
 IN TIERS. 2014 FBC-B TABLE 406.5.4.
  
 1B)(2) THE PLANS DO NOT PROVIDE THE AREA OF OPENNESS
 REQUIRED TO CONSIDER THIS STRUCTURE AS AN OPEN PARKING
 GARAGE PER SECTION 2014 FBC-B 406.5.2 PLEASE PROVIDE.
 SHEET AP.20 PROVIDES CALCULATIONS FOR THE OPENINGS IN
 THE EXTERIOR WALL. WHAT THE EXTERIOR WALL CALCULATIONS
 DOES NOT PROVIDE SEE SHEET AP.46 WALL SECTIONS WITH
 FIXED LOUVERS AND SCREEN PANELS. PLEASE PROVIDE FROM
 THE MANUFACTURERS OF BOTH THE FIXED LOUVER AND SCREEN
 WHAT THE NET FREE AREA WOULD BE FOR EACH OPENING. THERE
 WILL BE A REDUCTION FOR THE LOUVER AS WELL AS THE
 SCREEN PLEASE PROVIDE THE NEW WALL OPENING SIZES WITH
 THE DOUBLE REDUCTION PROVIDING A NET CLEAR OPENING,
 PERCENTAGE OF WALL VERSES OPENING.
  
 1B)(3) SHEET AP.20 DOES PROVIDE THE CALCULATIONS FOR
 THE EXTERIOR WALL, TO BE RECALCULATED BUT DOES NOT
 PROVIDE THE CALCULATION FOR THE INTERIOR WALL. 2014
 FBC-B 406.5.2. INTERIOR WALLS SHALL BE NOT LESS THAN 20
 PERCENT OPEN WITH UNIFORMLY DISTRIBUTED OPENINGS.
  
 1C)(1) SHEET G.01/ COVERSHEET LIST THE HEIGHT UNLIMITED
 AND AREA AS UNLIMITED. PLEASE REVIEW TABLE 406.5.4.
 ONLY BUILDING TYPE IA ALLOWS FOR UNLIMITED HEIGHT AND
 UNLIMITED AREA PLEASE ADDRESS.
  
 1C)(2) IF THE DESIGNER OF RECORD IS CLAIMING UNLIMITED
 ALLOWABLE AREA AS PER CODE SECTION 406.5.5 PLEASE
 PROVIDE CALCULATIONS SHOWING COMPLIANCE.
  
 1D) SHEET G.01/ COVERSHEET LIST TABLE 601
 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING
 ELEMENTS
 LIST THE REQUIRED FIRE RATINGS FOR A BUILDING TYPE IB
 NOT A BUILDING TYPE IIB? ADDITIONAL INFORMATION
 REQUIRED DISCREPANCY IN PLANS. 107.2.1.3.
  
 ? 1E) SHEET G.01/ COVERSHEET NOR SHEET A100 THE SITE
 PLAN SHOW AN ASSUMED PROPERTY LINE TO THE EAST OR WEST
 OF THE BUILDING FOR FIRE RESISTANCE RATING REQUIREMENTS
 FOR EXTERIOR WALLS BASED ON FIRE SEPARATION FBC-B TABLE
 601 & ALLOWABLE OPENINGS FOR UNPROTECTED,
 NON-SPRINKLERED BUILDINGS FBC-B TABLE 705.8 .
 ? 406.5.6 FIRE SEPARATION DISTANCE. EXTERIOR WALLS AND
 OPENINGS IN EXTERIOR WALLS SHALL COMPLY WITH TABLES 601
 AND 602. THE DISTANCE TO AN ADJACENT LOT LINE SHALL BE
 DETERMINED IN ACCORDANCE WITH TABLE 602 AND SECTION
 705.
  
 2) THIS BUILDING IS A 4 STORY/ 4 TIER BUILDING.
 THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) SHEET AP5.1 SHOWS FROM THE GROUND FLOOR TO THE TOP
 FLOOR THERE IS MORE THAN 30 FEET, STANDPIPES ARE
 REQUIRED. 2014 FBC-B 406.5.8 STANDPIPE SYSTEM. AN OPEN
 PARKING GARAGE SHALL BE EQUIPPED WITH A STANDPIPE
 SYSTEM AS REQUIRED BY SECTION 905.3 .
  
 2014 FBC-B 905.3.1 HEIGHT. CLASS III STANDPIPE SYSTEMS
 SHALL BE INSTALLED THROUGHOUT BUILDINGS WHERE THE FLOOR
 LEVEL OF THE HIGHEST STORY IS LOCATED MORE THAN 30 FEET
 (9144 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS, OR WHERE THE FLOOR LEVEL OF THE LOWEST
 STORY IS LOCATED MORE THAN 30 FEET (9144 MM) BELOW THE
 HIGHEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS.
  
 4) SHEET AP.53 DETAIL # 4:
  
 4A) THE TRIANGULAR AREA BETWEEN THE BOTTOM RAIL AND
 TREAD/ RISER MUST COMPLY WITH 2014 FBC-B OPENING
 LIMITATIONS, EXCEPTION # 2. THE TRIANGULAR OPENINGS AT
 THE OPEN SIDES OF A STAIR, FORMED BY THE RISER, TREAD
 AND BOTTOM RAIL SHALL NOT ALLOW PASSAGE OF A SPHERE 6
 INCHES.
  
 4B) THE GUARDRAIL SYSTEM LEAVES A CLEAR SPACE BETWEEN
 RUNGS OF A 4 INCH CLEAR SPACE. 2014 FBC-B OPENING
 LIMITATIONS, REQUIRED GUARDS SHALL NOT HAVE OPENINGS
 WHICH ALLOW PASSAGE OF A SPHERE 4 INCHES (102 MM) IN
 DIAMETER FROM THE WALKING SURFACE TO THE REQUIRED GUARD
 HEIGHT.
  
 4C) NOTE, THE GUARDRAIL WILL NEED TO BE REDRAWN, PLEASE
 PROVIDE A DETAIL THAT WILL ALSO SHOW COMPLIANCE WITH
 2014 FBC-B OPENING LIMITATIONS EXCEPTION # 1 FROM A
 HEIGHT OF 36 INCHES (914 MM) TO 42 INCHES (1067 MM),
 GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW PASSAGE OF A
 SPHERE 43/8 INCHES (111 MM) IN DIAMETER.
  
 5) SHEET AP.51 DETAIL # 1 AND SHEET AP.52 DETAIL # 2
 BOTH ALLOW A PERSON TO WALK BACK IN UNDER THE STAIRS,
 PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE SECTION 307.4 AND FIGURE 307.4.
  
 6A) SHEET AP.50 SHOWS DETAILS 1-4 WITH THE ELEVATOR
 CAR, PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 3002.4
 ELEVATOR CARS ARE TO ACCOMMODATE AMBULANCE STRETCHER
 REQUIREMENTS. 24 INCHES X 76 INCHES WITH NOT LESS THAN
 5 INCH RADIUS CORNERS.
  
 6B) SHEET AP.50 ELEVATOR DETAILS ARE TO COMPLY WITH THE
 ELEVATOR CAR COMPLYING WITH THE AMBULANCE STRETCHER
 REQUIREMENT WILL ALSO BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE). THE SYMBOL SHALL NOT BE LESS THAN 3
 INCHES IN HEIGHT AND SHALL BE PLACED ON BOTH SIDES OF
 THE HOISTWAY DOOR FRAME. FBC-B 3002.4.
  
 7) SHEET AP.46 DETAIL # 2,3 & 4 SHOWS AWNINGS, THERE IS
 NO DETAIL AS TO MATERIAL AND OR FRAMEWORK FOR THE
 AWNINGS NOR WIND DESIGN CRITERIA? 2014 FBC-B FABRIC
 AWNINGS IN COMPLIANCE WITH 3105.4 OR RIGID AWNINGS IN
 COMPLIANCE WITH 3105.5?
  
 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SWING & OVERHEAD GARAGE DOOR.
 (C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 9) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  