Plan Review Notes For Permit 15100819 |
Permit Number |
15100819 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-11-13 12:53:24 | 1) INDICATE ON THE GAS PLAN THE SPECIFIC GAS SIZING | | TABLES THAT WERE USED IN THE SIZING OF THE GAS SYSTEM. | | SUBMIT COPIES OF THE TABLES USED IF DIFFERENT THAN IN | | THE 2014 FBC-FUEL GAS. 2ND REQUEST. | | 2) IS THE POOL HEATER THE ONLY GAS APPLIANCE BEING | | INSTALLED UNDER THIS PERMIT OR ARE ALL THESE APPLIANCES | | BEING INSTALLED UNDER THIS GAS APPLICATION? IF THE POOL | | HEATER IS THE ONLY NEW APPLIANCE, MARK ALL THE OTHER | | APPLIANCES AS "EXISTING". ALSO, THE BBQ IS SHOWN ON THE | | LIST BUT NOT ON THE GAS DRAWING. CLARIFY.2ND REQUEST. | | 3) SIZE THE BRANCH LINE TO THE RANGE AND ALSO FOR THE | | HEATER BY THE METER.2ND REQUEST. | | 4) IF ALL APPLIANCES ARE BEING INSTALLED AT THIS TIME, | | SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL APPLIANCES. | | APPLIANCES SHALL BE LISTED AND LABELELD 2014 FBC-RES. | | SEC.G2404.3.2ND REQUEST. | | 5) SIZE THE BRANCH LINE TO THE RANGE AND ALSO FOR THE | | HEATER BY THE METER.2ND REQUEST. | | | | | | | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|