Plan Review Notes
Plan Review Notes For Permit 15100819
Permit Number 15100819
Review Stop G
Sequence Number 2
Notes
Date Text
2015-11-13 12:53:241) INDICATE ON THE GAS PLAN THE SPECIFIC GAS SIZING
 TABLES THAT WERE USED IN THE SIZING OF THE GAS SYSTEM.
 SUBMIT COPIES OF THE TABLES USED IF DIFFERENT THAN IN
 THE 2014 FBC-FUEL GAS. 2ND REQUEST.
 2) IS THE POOL HEATER THE ONLY GAS APPLIANCE BEING
 INSTALLED UNDER THIS PERMIT OR ARE ALL THESE APPLIANCES
 BEING INSTALLED UNDER THIS GAS APPLICATION? IF THE POOL
 HEATER IS THE ONLY NEW APPLIANCE, MARK ALL THE OTHER
 APPLIANCES AS "EXISTING". ALSO, THE BBQ IS SHOWN ON THE
 LIST BUT NOT ON THE GAS DRAWING. CLARIFY.2ND REQUEST.
 3) SIZE THE BRANCH LINE TO THE RANGE AND ALSO FOR THE
 HEATER BY THE METER.2ND REQUEST.
 4) IF ALL APPLIANCES ARE BEING INSTALLED AT THIS TIME,
 SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL APPLIANCES.
 APPLIANCES SHALL BE LISTED AND LABELELD 2014 FBC-RES.
 SEC.G2404.3.2ND REQUEST.
 5) SIZE THE BRANCH LINE TO THE RANGE AND ALSO FOR THE
 HEATER BY THE METER.2ND REQUEST.
  
  
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  