Plan Review Notes For Permit 15100811 |
Permit Number |
15100811 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-12-07 13:27:34 | PLAN | | REVIEW COMMENTS | | 2ND REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE POOL IS LOCATED IN AN AREA THAT IS KNOWN TO | | CONTAIN QUESTIONABLE SOILS. SUBMIT TWO COPIES OF A SOIL | | TEST IN COMPLIANCE WITH FBC-R401.4 FOR THE PROPOSED | | POOL. | | | | 2) THE POOL IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | (FLOOD ZONE A5). THE POOL EQUIPMENT IS REQUIRED TO BE | | LOCATED AT OR ABOVE A BASE FLOOD ELEVATION OF 7.5' | | NGVD. FBC-R322 |
|