Plan Review Notes For Permit 15100811 |
Permit Number |
15100811 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-27 10:40:58 | 1) SUBMIT A SET OF POOL PLANS THAT ARE CLEAR IN DETAIL | | AND REFLECT THE SCOPE OF WORK TO BE DONE. THE PIPING | | PLANS HAVE ITEMS CROSSED OFF, PORTIONS ARE DIFFICULT TO | | READ,AND I CANNOT DETERMINE WHAT IS AND WHAT IS NOT | | BEING INSTALLED. SUBMIT PLANS WITH CLEAN PIPING | | DRAWINGS WTHOUT ITEMS CROSSED OFF THAT CLEARLY SHOW | | WHAT IS BEING INSTALLED. | | 2) THE PIPING DIAGRAM FOR THE SPA SHOWS 2 MAIN DRAINS | | AND THE PLAN VIEW SHOWS ONE. CLARIFY.THE SPA DETAIL ON | | SHEET 1 SHOWS 2-8" MAIN DRAINS ALSO. | | 3) SKIMMER & VAC DETAIL REFERS TO 2010 FBC. THE CODE IN | | EFFECT IS THE 2014 FBC-RESIDENTIAL. | | 4) THE PIPING SCHEMATIC SHOWS THE SUCTION PIPING FOR | | THE SPA AS 2" BUT THE PLAN VIEW SHOWS 3". THERE IS ALSO | | A NOTE ON THE PLANS THAT STATES ALL SUCTION PIPING TO | | BE 2". CLARIFY. | | 5) THERE IS A NOTE ON THE PLANS THAT STATES THE MAXIMUM | | SUCTION PIPE VELOCITY IS SIX FEET PER SECOND BUT THE | | APSP/ANSI-7 WORKSHEET NOTES THE SUCTION VELOCITY AS 8 | | FPS. CLARIFY. | | 6) SHOW THE PIPE SIZE FOR THE DECK JETS. WPB AMEND. TO | | FBC SEC. 107.2.1. | | 7) SHT. HP-1 IS ILLEGIBLE.SUBMIT A PLAN THAT IS CLEAR | | IN DETAIL AND REFLECTS WHAT IS TO BE DONE. WPB AMEND. | | TO FBC SEC. 107.2.1. | | | | PLEASE DO NOT SUBMIT A PLAN OF THIS QUALITY IN THE | | FUTURE. PLANS THAT SHOW ITEMS CROSSED OFF AND ARE NOT | | CLEAR IN THE SCOPE OF WORK WILL BE REJECTED. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|