Plan Review Notes
Plan Review Notes For Permit 15100811
Permit Number 15100811
Review Stop P
Sequence Number 1
Notes
Date Text
2015-10-27 10:40:581) SUBMIT A SET OF POOL PLANS THAT ARE CLEAR IN DETAIL
 AND REFLECT THE SCOPE OF WORK TO BE DONE. THE PIPING
 PLANS HAVE ITEMS CROSSED OFF, PORTIONS ARE DIFFICULT TO
 READ,AND I CANNOT DETERMINE WHAT IS AND WHAT IS NOT
 BEING INSTALLED. SUBMIT PLANS WITH CLEAN PIPING
 DRAWINGS WTHOUT ITEMS CROSSED OFF THAT CLEARLY SHOW
 WHAT IS BEING INSTALLED.
 2) THE PIPING DIAGRAM FOR THE SPA SHOWS 2 MAIN DRAINS
 AND THE PLAN VIEW SHOWS ONE. CLARIFY.THE SPA DETAIL ON
 SHEET 1 SHOWS 2-8" MAIN DRAINS ALSO.
 3) SKIMMER & VAC DETAIL REFERS TO 2010 FBC. THE CODE IN
 EFFECT IS THE 2014 FBC-RESIDENTIAL.
 4) THE PIPING SCHEMATIC SHOWS THE SUCTION PIPING FOR
 THE SPA AS 2" BUT THE PLAN VIEW SHOWS 3". THERE IS ALSO
 A NOTE ON THE PLANS THAT STATES ALL SUCTION PIPING TO
 BE 2". CLARIFY.
 5) THERE IS A NOTE ON THE PLANS THAT STATES THE MAXIMUM
 SUCTION PIPE VELOCITY IS SIX FEET PER SECOND BUT THE
 APSP/ANSI-7 WORKSHEET NOTES THE SUCTION VELOCITY AS 8
 FPS. CLARIFY.
 6) SHOW THE PIPE SIZE FOR THE DECK JETS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 7) SHT. HP-1 IS ILLEGIBLE.SUBMIT A PLAN THAT IS CLEAR
 IN DETAIL AND REFLECTS WHAT IS TO BE DONE. WPB AMEND.
 TO FBC SEC. 107.2.1.
  
 PLEASE DO NOT SUBMIT A PLAN OF THIS QUALITY IN THE
 FUTURE. PLANS THAT SHOW ITEMS CROSSED OFF AND ARE NOT
 CLEAR IN THE SCOPE OF WORK WILL BE REJECTED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  