Plan Review Notes For Permit 15100811 |
Permit Number |
15100811 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-27 10:54:15 | 1) THE GAS HEATER SHALL HAVE A MINIMUM THERMAL | | EFFICIENCY OF 82%.THE SUBMITTED SPECIFICATION SHEET | | DOES NOT SHOW THIS REQUIREMENT. SUBMIT POOL HEATER | | SPECS THAT SHOW COMPLIANCE. 2014 FBC-ENERGY CODE | | SEC.R403.9.1.1. | | 2) GAS POOL HEATERS SHALL NOT HAVE CONTINUOUSLY BURNING | | PILOT LIGHTS.2014 FBC-ENERGY CODE SEC.R403.9.1.1. | | SUBMIT SPECIFICATIONS THAT SHOW COMPLIANCE. | | 3) IDENTIFY THE MODEL OF THE POOL HEATER TO BE | | INSTALLED ON THE MANUF. SPECIFICATIONS. | | 4) SIZE ALL SECTIONS OF THE GAS PIPING DIAGRAM AND | | CLEARLY SHOW THE TYPE OF PIPE BEING INSTALLED.WPB | | AMEND. TO FBC SEC. 107.2.1. | | 5) THE GAS DRAWING IS ILLEGIBLE.SUBMIT A GAS RISER THAT | | IS CLEAR IN DETAIL AND SHOWS ALL PIPE SIZES, PIPE | | MATERIALS AND BTU LOAD OF EACH APPLIANCE. WPB AMEND. TO | | FBC SEC. 107.2.1. | | SEE ALSO APPLICATION #15100819 | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|