Plan Review Notes
Plan Review Notes For Permit 15100811
Permit Number 15100811
Review Stop G
Sequence Number 1
Notes
Date Text
2015-10-27 10:54:151) THE GAS HEATER SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82%.THE SUBMITTED SPECIFICATION SHEET
 DOES NOT SHOW THIS REQUIREMENT. SUBMIT POOL HEATER
 SPECS THAT SHOW COMPLIANCE. 2014 FBC-ENERGY CODE
 SEC.R403.9.1.1.
 2) GAS POOL HEATERS SHALL NOT HAVE CONTINUOUSLY BURNING
 PILOT LIGHTS.2014 FBC-ENERGY CODE SEC.R403.9.1.1.
 SUBMIT SPECIFICATIONS THAT SHOW COMPLIANCE.
 3) IDENTIFY THE MODEL OF THE POOL HEATER TO BE
 INSTALLED ON THE MANUF. SPECIFICATIONS.
 4) SIZE ALL SECTIONS OF THE GAS PIPING DIAGRAM AND
 CLEARLY SHOW THE TYPE OF PIPE BEING INSTALLED.WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) THE GAS DRAWING IS ILLEGIBLE.SUBMIT A GAS RISER THAT
 IS CLEAR IN DETAIL AND SHOWS ALL PIPE SIZES, PIPE
 MATERIALS AND BTU LOAD OF EACH APPLIANCE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 SEE ALSO APPLICATION #15100819
  