Plan Review Notes
Plan Review Notes For Permit 15100806
Permit Number 15100806
Review Stop G
Sequence Number 1
Notes
Date Text
2015-10-24 03:01:141) THE NOTES ON THE PLAN STATE THIS IS A 2 PSI SYSTEM
 BUT THE TABLE YOU ARE REFERENCING FROM THE 2014
 FBC-RES. ON THE PLANS IS FOR LESS THAN 2 PSI WITH A
 PRESSURE DROP OF 3.0 IN. W.C.. CLARIFY.
 2) IF IT IS A 2 PSI SYSTEM, INDICATE THE CORRECT SIZING
 TABLE FOR THE SYSTEM ON THE PLAN.2014 FBC-FUEL GAS.
 SEC.402.2.
 3) SIZE ALL SECTIONS OF THE PIPE ON THE RISER DIAGRAM.
 THE ONLY PIPE THAT IS SIZED IS THE 3/4" CSST TO THE
 RANGE, 2014 FGC SEC. 402.2.
 4) SUBMIT MANUF. SPECS FOR THE DRYER AND RANGE.
 APPLIANCES SHALL BE LISTED AND LABELED. SEC. 301.3.
 5) IF THE DRYER IS LOCATED IN A CLOSET, MAKEUP AIR
 SHALL BE PROVIDED. AN OPENING HAVING AN AREA OF NOT
 LESS THAN 100 SQUARE INCHES FOR MAKEUP AIR SHALL BE
 PROVIDED IN THE CLOSET ENCLOSURE OR MAKEUP AIR SHALL BE
 PROVIDED BY OTHER APPROVED MEANS. 2014 FGC SEC.304.1,
 614.5. SHOW THE LOCATION OF THE DRYER ON THE FLOOR
 PLANS.
 6) SHOW THE LOCATION OF ALL STEP-DOWN REGULATORS IF IT
 IS A 2 PSI SYSTEM. SHOW THE LOCATION OF THE REGULATOR
 VENTS AND THE SIZES.COMPLY W/ 2014 FGC SEC.410.2. &
 410.3.
 7) IF THE TANKLESS WATER HEATER IS REPLACING AN
 EXISTING STORAGE TANK TYPE, INDICATE SUCH ON THE PLANS.
 IF THE TANKLESS IS IN ADDITION TO AN EXISTING WATER
 HEATER, SUBMIT A WATER RISER DIAGRAM SHOWING WHERE THE
 COLD WATER SUPPLY IS COMING FROM.MINIMUM COLD WATER
 SUPPLY SHALL BE 3/4".
 8) A SEPARATE PERMIT IS REQUIRED FOR ANY RELATED
 ELECTRICAL WORK THAT WILL BE DONE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  