2015-11-05 13:34:101ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100773
 11/5/2015
  
 1) DUE TO CHANGES IN THE FLOOR PLAN, THE AHU-1 IS NOW
 SHOWN TO BE LOCATED ABOVE THE WOMEN'S TOILET ROOM
 SUSPENDED CEILING. PLEASE REFER TO SECTION 306.1 AND
 INDICATE HOW ACCESS FOR INSPECTION, SERVICE, REPAIR,
 AND REPLACEMENT WILL BE ACCOMPLISHED WITHOUT REMOVING
 PERMANENT CONSTRUCTION.
 2) SHOW THE AC CONDENSATE PIPING RUNS AND DISCHARGE
 LOCATIONS.
 3) THE AC SYSTEM DATA FOR COOLING CAPACITY AND SEER
 LISTED IN THE SCHEDULE ON M0.1 DOES NOT MATCH THE DATA
 LISTED UNDER SYSTEM REPORT COMPLIANCE IN THE ENERGY
 CONSERVATION FORM SUBMITTAL: PLEASE CORRECT.
  