2015-10-30 13:07:26 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1. SHEET E 0.1, PROVIDES NO READILY IDENTIFIABLE | | INDICATION OF FIRE ALARM WORK. THE EXTENT OF THE | | REMODEL OR REVISION IS UNCLEAR AND DOES NOT INDICATE | | SUFFICIENT DETAIL TO ADDRESS THE FIRE ALARM OF THE | | PROPOSED PROJECT. | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | 2. SHEET P 1.1, INDICATES INFORMATION REGARDING GREASE | | AND GREASE TRAPS. THERE IS TO BE NO COOKING OF ANY | | PRODUCT PRODUCING GREASE LADEN VAPORS WITHOUT A NFPA 96 | | COMPLIANT HOOD AND FIRE SUPRESSION SYSTEM. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|