2015-12-01 15:13:34 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1. REVISE/CORRECT YOUR GENERAL NOTES #3. AMBIENT |
| CONDITIONS AND NOT CONDUCTOR SIZING DICTATE INSULATION |
| REQUIREMENTS. |
| 2. NEC 110.16 ALL ELECTRICAL EQUIPMENT SHALL BE LABELED |
| TO WARN SERVICED PERSONNEL AGAINST AN ARCH-FLASH |
| HAZARD. |
| 3. NEC 600.5 EVERY COMMERCIAL ESTABLISHMENT ACCESSIBLE |
| TO PEDESTRIANS SHALL HAVE AT EVERY PEDESTRIAN ENTRY AT |
| LEAST ONE OUTLET IN AN ACCESSIBLE LOCATION FOR SIGNAGE. |
| 4. NEC 406.9(B) 15 & 20 AMP 125 - 250 VOLT NON-LOCKING |
| TYPE RECEPTACLES INSTALLED IN "WET LOCATIONS" SHALL BE |
| RATED WEATHER RESISTANT "WR". |
| 5. ADDITIONAL EMERGENCY LIGHTING SHALL BE INSTALLED IN |
| THE DINNING, PREP POS AND PATIO AREAS. |
| 6. NEC 210.8(B) ALL 15 & 20 AMP 125 VOLT RECEPTACLES |
| INSTALLED IN KITCHENS SHALL BE GFCI PROTECTED. |
| 7. NEC 250.94 AN INTER-SYSTEM BONDING TERMINAL SHALL BE |
| INSTALLED. |
| 8. THE FEEDER TO PANEL ?H? EXCEEDS THE MAXIMUM 3% |
| VOLTAGE DROP. 3/0 CU FOR 200 AMP AT 150 FT. |
| 9. NEC 406.9(B) DETAIL #7 SHALL INDICATE AN ?IN-USE? |
| TYPE COVER AS INDICATED |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |