Plan Review Notes
Plan Review Notes For Permit 15100773
Permit Number 15100773
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-09 11:28:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100773
 ADD: 328 FERN ST.
 CONT: L. J. SHEEHAN, INC.
 TEL: (561)223-2750
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV.09/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A WRITTEN RESPONSE TO WHAT IS THE
 CORRECT ADDRESS. THE CITY OF WEST PALM BEACH AND THE P.
 B. C. PROPERTY APPRAISERS OFFICE BOTH LIST UNDER THE
 PCN 74-43-43-21-01-009-0070 AS 326 FERN ST. THE PLANS
 ALL HAVE THE ADDRESS AS 326 FERN ST. THE PERMIT
 APPLICATION HAS THE ADDRESS AS 328 FERN ST. THE CITY
 ALSO HAS A TENANT ADDRESS OF 328 FERN ST. IF THIS
 PROJECT IS GOING TO USE THE ADDRESS OF 328 FERN ST. THE
 PLANS WILL NEED TO BE REPRINTED TO THE CORRECT ADDRESS.
 IF THE 326 FERN ST. THEN A TENANT SUITE NUMBER WILL
 NEED TO BE DETERMINED. FOR A LIST OF EXISTING SUITE
 NUMBERS FOR THE 1ST FLOOR YOU WOULD NEED TO CONTACT
 SANDY WURAFTIC AT 561-805-6688.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED.
  
 2) NOTICE, NO ACTION IS REQUIRED. THIS IS A RESTAURANT,
 A BUSINESS OCCUPANCY, OCCUPANT LOAD OF LESS THAN 50, NO
 IMPACT FEES ARE DUE, P. B. C. IMPACT FEES OFFICE.
 IMPACT FEES WERE PAID FOR RETAIL (MERCANTILE
 OCCUPANCY). TRACKING NUMBER MU-2013-023597-0000.
  
 3) SHEET S-1 PROVIDES THE WIND DESIGN CRITERIA TO BE
 UNDER THE 2014 FBC-B, 5TH EDITION BUT THE PRESSURES
 SEEM A LITTLE LOW FOR A MEAN ROOF HEIGHT OF 87 FEET.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS & MULLIONS.
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6) SHEET A-0.00 SHOWS DOOR TO RESTROOMS 106 & 107.
 SHEET A-6.01 THE DOOR SCHEDULE INDICATES THESE DOORS TO
 BE 2'-10" IN WIDTH. A 3'-0" DOOR WIDTH IS REQUIRED TO
 OBTAIN A 32 INCH CLEAR OPENING. 2014 FBC-B 1008.1.1
 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 7) SHEET A2.01 INDICATES A DETAIL 4 /A5.10 THE SERVICE
 COUNTER TO BE 40 INCHES TALL. PLEASE SHOW COMPLIANCE
 WITH THE 2014 ACCESSIBILITY CODE EITHER 904.4.1PARALLEL
 APPROACH OR 904.4.2 FRONTAL APPROACH.
  
 8) SHEET A2.01 ALSO WILL NEED TO SHOW THE HEIGHT FOR
 ACCESSIBLE TABLES IN COMPLIANCE WITH 2014 ACCESSIBILITY
 CODE 902.3. PLEASE SHOW COMPLIANCE WITH 226.1 AND
 226.2.
  
 9) PLEASE NOTE SHEET M5.1 THE NEW ROOF TOP UNIT C-2
 WIND DESIGN CRITERIA APPEARS TO BE FOR A BUILDING ,
 THAN 60 FEET TALL. THIS BUILDING MEAN ROOF HEIGHT IS 87
 FEET IN HEIGHT. ALSO NOTE SHEET M1.2 INDICATES THIS
 UNIT IS TO TIE DOWN TO A EXISTING ROOF RACK NOT A CURB
 AS INDICATED ON M5.1.
 M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  