2016-01-05 14:06:202ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ACCORDING TO FBC TABLE 1004.1.2 YOUR OCCUPANT LOAD
 IS 18 PEOPLE ACCORDING TO FBC PL TABLE 403.1 IN B
 OCCUPANCY'S WITH OVER 15 PEOPLE A SERVICE SINK IS
 REQUIRED. THIS IS THE SECOND REQUEST FOR THIS.
 2. SHEETS A.01- A.03 AND E1 SHOW SINGLE WATER FOUNTAIN
 ON P1 YOU SHOW A DOUBLE OR HILO PLEASE CLARIFY.
 3. PLEASE SHOW THAT THE WATER FOUNTAIN COMPLIES WITH
 FBC ACC SEC 307.2 PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH
 FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM)
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH.
  