Plan Review Notes For Permit 15100764 |
Permit Number |
15100764 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-12-29 11:16:10 | 2ND REVIEW 2014 MECHANICAL | | PERMIT #15100764 | | 12/29/15 | | | | 1) THE NEW TENANT OCCUPANCY, WHETHER IT IS BUSINESS AS | | SPECIFIED ON A.01 AND A.04, OR S-2 AS SPECIFIED ON THE | | A.04 LS PLAN REQUIRES A MEANS OF VENTILATION IN | | ACCORDANCE WITH SECTION 401.2 AND TABLE 403.3 FBC-14 | | MECHANICAL. AS PREVIOUSLY REQURESTED IN THE 1ST REVIEW, | | PROVIDE VENTILATION CALCULATIONS AND A VENTILATION | | SYSTEM. PLEASE NOTE THAT IF THE OCCUPANCY IS TO BE | | BUSINESS THEN AN ACTIVE OR PASSIVE SPACE-HEATING SYSTEM | | CAPABLE OF MAINTAINING A MINIMUM INDOOR TEMPERATURE OF | | 68 DEGREES F IS REQUIRED- SECTION 309.1 FBC-14 | | MECHANICAL, | | 2) AS PREVIOUSLY NOTED IN THE 1ST REVIEW THIS IS A | | CHANGE OF OCCUPANCY FROM F-1 TO EITHER A B OR S-2 | | OCCUPANCY, WHICH REQUIRES COMPLIANCE WITH SECTION | | C101.4.4 FBC-14 ENERGY CONSERVATION. THE REMOVAL OF THE | | AC SYSTEM DOES NOT EXEMPT THE SPACE FROM MEETING | | COMPLIANCE- SEE SECTION C101.4.8 FBC-14 ENERGY | | CONSERVATION AND SUBMIT ENERGY CALCULATIONS USING | | EITHER THE PERFORMANCE OR PRESCRIPTIVE BASED METHOD- | | SECTION C101.5. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|