2016-01-04 06:53:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100764
 ADD: 1100 W. TECHNOLOGY PL. SUITE # 110
 CONT: HEDRICK BROS. CONSTRUCION
 TEL: (561)689-8880
 E-MAIL: ???????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 04/2016
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS INDICATES THIS TENANT SPACE IS A
 CHANGE OF OCCUPANCY FROM A F1 OCCUPANCY, A DRY CLEANING
 FACILITY WHERE THERE WAS A BOILER, NOT JUST A DROP OFF
 AND PICK UP FACILITY. PERMIT # 99111358 SHOULD A FULL
 SCALE DRY CLEANING FACILITY, THE NEW OCCUPANCY IS
 INDICATED AS A BUSINESS OCCUPANCY. SHEET A0.2 & M1.1
 BOTH SHOW THIS SPACE TO NOW BE NON-CONDITIONED SPACE.
  
 PLEASE SHOW HOW THE BUSINESS/ STORAGE OCCUPANCY WILL
 MEET THE CODE SECTION OF:
 2014 FBC-B 1203.4. 1203.4 NATURAL VENTILATION. NATURAL
 VENTILATION OF AN OCCUPIED SPACE SHALL BE THROUGH
 WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO THE
 OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS
 SHALL BE PROVIDED WITH READY ACCESS SO THAT THE
 OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING
 OCCUPANTS.
  
 1203.4.1 VENTILATION AREA REQUIRED. THE OPENABLE AREA
 OF THE OPENINGS TO THE OUTDOORS SHALL BE NOT LESS THAN
 4 PERCENT OF THE FLOOR AREA BEING VENTILATED.
  
  
  
  
 2) AS PREVIOSLY NOTED IN THE 1ST REVIEW, THIS IS A
 CHANGE OF OCCUPANCY FROM A (F-1 FACTORY) TO A BUSINESS
 OCCUPANCY, WHICH REQUIRES COMPLIANCE WITH SECTION:
  
 C101.4.4 OF THE 2014 FBC-ENERGY CONSERVATION CODE.
 C101.4.4 CHANGE IN OCCUPANCY OR USE. SPACES UNDERGOING
 A CHANGE IN OCCUPANCY THAT WOULD RESULT IN AN INCREASE
 IN DEMAND FOR EITHER FOSSIL FUEL OR ELECTRICAL ENERGY
 SHALL COMPLY WITH THIS CODE. WHERE THE USE IN A SPACE
 CHANGES FROM ONE USE IN TABLE C405.5.2(1) OR (2) TO
 ANOTHER USE IN TABLE C405.5.2(1) OR (2), THE INSTALLED
 LIGHTING WATTAGE SHALL COMPLY WITH SECTION C405.5.
  
 3) COMPLIED. N/A.
  
 4)COMPLIED. N/A.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  