2015-10-27 10:59:02 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | | | 1. SERVICE SINK REQUIRED IN B OCCUPANCY WITH OCCUPENCY | | LOAD OF OVER 15 PER FBC P TABLE 403.1 YOUR OCCUPANT | | LOAD FACTOR FOR BUSINESS IS 100 GROSS PER FBC TABLE | | 1004.1.2 WITCH GIVES YOU 18 . | | 2. GRAB BARS SHALL COMPLY WITH FBC ACC. SEC 609.4 | | POSITION OF GRAB BARS. | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | THE GRIPPING SURFACE, | | 3. TOILETS SHALL COMPLY WITH FBC ACC SEC 604.2 | | LOCATION. | | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM | | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL | | 4. TOILET PAPER DISPENCER SHALL COMPLY WITH FBC ACC SEC | | 604.7 DISPENSERS. | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 | | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND | | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL | | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES | | NOT ALLOW CONTINUOUS PAPER FLOW. |
|