2015-11-03 16:51:591ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100764
 11/3/15
  
 1) ENERGY CALCULATIONS ARE REQUIRED PER SECTIONS
 C101.4.4 AND C101.4.5 FBC-14 ENERGY CONSERVATION.
 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND
 PROVIDE VENTILATION CALCULATIONS IN COMPLIANCE WITH
 TABLE 403.3 FBC-14 MECHANICAL.
 3) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 THE RTU AND CURB ATTACHMENT TO THE EXISTING STRUCTURE.
 THE ENGINEER OF RECORD SHALL PROVIDE THE WIND LOAD
 DESIGN CRITERIA AND DESIGN PRESSURES ON THE PLANS.
 SECTION CUTS OF THE ROOF STRUCTURE, CURB, AND RTU SHALL
 BE PLACED ON THE PLAN TO CLEARLY INDICATE ALL REQUIRED
 STRUCTURAL REINFORCEMENTS AND ATTACHMENTS.
 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW RTU-
 REFER TO SECTION 307
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER