Plan Review Notes For Permit 15100764 |
Permit Number |
15100764 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-11-03 16:51:59 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15100764 | | 11/3/15 | | | | 1) ENERGY CALCULATIONS ARE REQUIRED PER SECTIONS | | C101.4.4 AND C101.4.5 FBC-14 ENERGY CONSERVATION. | | 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND | | PROVIDE VENTILATION CALCULATIONS IN COMPLIANCE WITH | | TABLE 403.3 FBC-14 MECHANICAL. | | 3) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR | | THE RTU AND CURB ATTACHMENT TO THE EXISTING STRUCTURE. | | THE ENGINEER OF RECORD SHALL PROVIDE THE WIND LOAD | | DESIGN CRITERIA AND DESIGN PRESSURES ON THE PLANS. | | SECTION CUTS OF THE ROOF STRUCTURE, CURB, AND RTU SHALL | | BE PLACED ON THE PLAN TO CLEARLY INDICATE ALL REQUIRED | | STRUCTURAL REINFORCEMENTS AND ATTACHMENTS. | | 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW RTU- | | REFER TO SECTION 307 | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|