Plan Review Notes
Plan Review Notes For Permit 15100764
Permit Number 15100764
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-19 17:07:36THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. FBC-E402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN
 THE BUILDING'S THERMAL ENVELOPE SHALL BE IC RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN THE CONDITIONED AND
 THE NON-CONDITIONED SPACE.
 2. FBC-E405.2.2.2, OCCUPANCY SENSORS SHALL BE INSTALLED
 IN ALL BATHROOMS 300 SQ. FT. OR LESS.
 3. FBC-B714.3, ALL OUTLETS AND/OR ELECTRICAL PANELS
 INSTALLED IN A FIRE RATED WALL SHALL COMPLY AS
 INDICATED.
 4. NEC210.63, THERE SHALL BE A 15 - 20 AMP SERVICE
 OUTLET WITHIN 25' OF THE HVAC EQUIPMENT.
 5. NEC300.5(B), THE INTERIOR OF A RACEWAY INSTALLED
 UNDERGROUND SHALL BE CONSIDERED A WET LOCATION AND
 THEREFORE THE FEEDER CONDUCTORS SHALL BE LISTED
 ACCORDINGLY.
 6. NEC410.36, LUMINAIRES INSTALLED ON FRAMING MEMBERS
 OF A SUSPENDED CEILING SHALL BE SECURELY FASTENED TO
 THE CEILING FRAMING MEMBERS BY MECHANICAL MEANS.
 7. NEC600.5, EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE
 AT EVERY ENTRY ACCESSIBLE TO PEDESTRIANS A DEDICATED
 SIGN OUTLET.
 8. NEC700.12(F), ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 CONNECTED TO THE ELECTRICAL CIRCUIT FOR THE AREA IN
 WHICH THEY ARE LOCATED. A DEDICATED EMERGENCY LIGHT
 CIRCUIT IS NOT ALLOWED BY CODE UNLESS THERE IS A
 MINIMUM OF THREE DIFFERENT CIRCUITS FOR THE AREA.
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  