2015-11-19 17:07:36 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| 1. FBC-E402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN |
| THE BUILDING'S THERMAL ENVELOPE SHALL BE IC RATED AND |
| SEALED TO LIMIT AIR LEAKAGE BETWEEN THE CONDITIONED AND |
| THE NON-CONDITIONED SPACE. |
| 2. FBC-E405.2.2.2, OCCUPANCY SENSORS SHALL BE INSTALLED |
| IN ALL BATHROOMS 300 SQ. FT. OR LESS. |
| 3. FBC-B714.3, ALL OUTLETS AND/OR ELECTRICAL PANELS |
| INSTALLED IN A FIRE RATED WALL SHALL COMPLY AS |
| INDICATED. |
| 4. NEC210.63, THERE SHALL BE A 15 - 20 AMP SERVICE |
| OUTLET WITHIN 25' OF THE HVAC EQUIPMENT. |
| 5. NEC300.5(B), THE INTERIOR OF A RACEWAY INSTALLED |
| UNDERGROUND SHALL BE CONSIDERED A WET LOCATION AND |
| THEREFORE THE FEEDER CONDUCTORS SHALL BE LISTED |
| ACCORDINGLY. |
| 6. NEC410.36, LUMINAIRES INSTALLED ON FRAMING MEMBERS |
| OF A SUSPENDED CEILING SHALL BE SECURELY FASTENED TO |
| THE CEILING FRAMING MEMBERS BY MECHANICAL MEANS. |
| 7. NEC600.5, EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE |
| AT EVERY ENTRY ACCESSIBLE TO PEDESTRIANS A DEDICATED |
| SIGN OUTLET. |
| 8. NEC700.12(F), ALL EMERGENCY AND EXIT LIGHTS SHALL BE |
| CONNECTED TO THE ELECTRICAL CIRCUIT FOR THE AREA IN |
| WHICH THEY ARE LOCATED. A DEDICATED EMERGENCY LIGHT |
| CIRCUIT IS NOT ALLOWED BY CODE UNLESS THERE IS A |
| MINIMUM OF THREE DIFFERENT CIRCUITS FOR THE AREA. |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |