2015-11-02 13:50:51 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15100764 |
| ADD: 1100 W. TECHNOLOGY PL. SUITE # 110 |
| CONT: HEDRICK BROS. CONSTRUCION |
| TEL: (561)689-8880 |
| E-MAIL: ??????? |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. NOV. 02/2014 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED PLANS INDICATES THIS TENANT SPACE IS A |
| CHANGE OF OCCUPANCY FROM A F1 OCCUPANCY, A DRY CLEANING |
| FACILITY WHERE THERE WAS A BOILER, NOT JUST A DROP OFF |
| AND PICK UP FACILITY. PERMIT # 99111358 SHOULD A FULL |
| SCALE DRY CLEANING FACILITY, THE NEW OCCUPANCY IS |
| INDICATED AS A BUSINESS OCCUPANCY. SHEET A0.2 & M1.1 |
| BOTH SHOW A NEW |
| RTU TO BE INSTALLED ON THE ROOF. |
| 2014 ENERGY CODE C101.4.5 CHANGE IN SPACE CONDITIONING. |
| ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME |
| CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO |
| FULL COMPLIANCE WITH THIS CODE. PLEASE PROVIDE HOW |
| COMPLIANCE WILL BE ACHIEVED? |
| |
| 2014 C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL |
| COMPLY WITH ONE OF THE FOLLOWING: |
| 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| NOTE THE OVERHEAD DOOR MAYBE REQUIRED TO BE INSULATED, |
| DEPENDING ON THE EMERGY CALCULATIONS. |
| |
| 2A) THE PLANS DO NOT INDICATE HOW THE ROOF IS GOING TO |
| BE FRAMED IN AROUND THE NEW ROOF TOP HOLE FOR THE NEW |
| RTU. PLEASE PROVIDE FRAMING MEMBERS REQUIRED, TYPE OF |
| MATERIALS, BAR JOIST WILL REQUIRE STIFFENERS IN THE BAR |
| JOIST, FRAMING DETAILS, AND PLEASE PROVIDE HOW THE NEW |
| ROOF TOP CURB WILL BE ANCHORED TO THE BAR JOIST AND |
| FRAMING MEMBERS. PLEAS ALSO PROVIDE A PRODUCT APPROVAL |
| FOR THE NEW ROOF TOP CURB FOR THE RTU UNIT. MWFRS MAIN |
| WIND FORCE RESISSTING SYSTEM AND 2014 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS |
| |
| 2B) THE PLANS DO NOT INDICATE HOW THE RTU ROOF TOP UNIT |
| IS GOING TO BE ATTACHED TO THE ROOF TOP CURB TO RESIST |
| LATERAL SLIDDING AND THE MOMENT OF OVERTURNING. PLEASE |
| PROVIDE DETAIL. 2014 FBC-B 1609.6.4.4.1. |
| |
| 3) THW PLANS DO NOT INDICATE THE ROOF ELEVATION NOR IF |
| THERE IS A PAREPET AND THE HEIGHT OF THE PAREPET. |
| APERMANENT LADDER MAYBE REQUIRED FOR ROOF TOP ACCESS, |
| PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B ? 1509.6.4 |
| EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| STRUCTURES. |
| WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| CRITERIA: |
| 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| INCHES (356 MM) ON CENTER. |
| 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN |
| 6-INCHES (152 MM) DEEP. |
| 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| BETWEEN RAILS. |
| 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| (136.1 KG) LOAD. |
| 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2). |
| 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610 |
| MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR |
| SERVICE PLATFORMS |
| |
| 4) THE OTHER ISSUE MAYBE THE ARCHITECTURAL PLANS DO NOT |
| PROVIE THE HEIGHT OF THE PARAPET WALL, ZONING MAY |
| REQUIRE THE A/C RTU ROOF TOP UNIT TOBE SCREENED. IF SO |
| PLEASE PROVIDE HOW THE FRAMEWORK WILL BE ATTACHED TO |
| THE MAINWIND FORCE RESISTING SYSTEM AND HOW THE WIND |
| SCREEN IS TO BE ATTACHED TO THE FRAME. WHAT WIND DESIGN |
| PERAMETERS ARE GOING TO BE USED TO FORMULATE THE |
| RELEASE OF THE FABRIC IN HIGH WIND EVENTS? |
| 1609.6.4.4.1/ 3105.4.2.1. |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |