Plan Review Notes For Permit 15100760 |
Permit Number |
15100760 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-28 08:52:25 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15100760 | | 10/28/15 | | | | 1) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE. | | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE | | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F | | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS | | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE | | HVAC SYSTEM. | | PLEASE REVISE THE PLAN TO INDICATE COMPLIANCE. | | 2) REFER TO SECTION 507.9 CLEARANCES FOR TYPE I HOOD, | | AND REVISE THE PLAN TO INDICATE COMPLIANCE. | | A TYPE I HOOD SHALL BE INSTALLED WITH A CLEARANCE TO | | COMBUSTIBLES OF NOT LESS THAN 18 INCHES (457 MM). | | EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM | | WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS | | WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES | | PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND | | NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD | | AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA | | EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL | | DIRECTIONS FROM THE HOOD. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|