2015-11-20 14:47:32 | RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED: | | A) REVISE THE DESIGN DATA. PROJECT IS NOT LOCATED IN | | SARASOTA. SEC. 107.2.1 CITY AMENDMENTS. | | | | B) REVISE THE COMPONENT DESCRIPTION ON PAGE 4 TO MATCH | | PLANS. SEE WINDOWS AND DOORS PRODUCT APPROVALS | | SUBMITTED, THERE IS NOT BLOCK WALL, THERE IS NOT FOAM | | INSULATION SPECIFIED ON PLANS, THERE IS NOT CONCRETE | | SLAB ON GRADE, THERE IS NOT 4 PEOPLE IN ONE BEDROOM | | UNIT., ETC. SEC. 107.2.1 CITY AMENDMENTS. IF EQUIPMENT | | SIZING NEEDS TO BE CHANGED, THEN CHANGE DRAWING M.1 AS | | WELL. | | | | 2- PROVIDE THE NAME AND SIGNATURE ON DRAWING M.1 OF THE | | PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. | | 107.2.1 CITY AMENDMENTS. | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ***PLEASE REMOVE ANY REVISED DRAWING. SUBMIT OLD COPIES | | (NOT STAPLED) FOR REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|