2015-11-20 14:47:32RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 A) REVISE THE DESIGN DATA. PROJECT IS NOT LOCATED IN
 SARASOTA. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) REVISE THE COMPONENT DESCRIPTION ON PAGE 4 TO MATCH
 PLANS. SEE WINDOWS AND DOORS PRODUCT APPROVALS
 SUBMITTED, THERE IS NOT BLOCK WALL, THERE IS NOT FOAM
 INSULATION SPECIFIED ON PLANS, THERE IS NOT CONCRETE
 SLAB ON GRADE, THERE IS NOT 4 PEOPLE IN ONE BEDROOM
 UNIT., ETC. SEC. 107.2.1 CITY AMENDMENTS. IF EQUIPMENT
 SIZING NEEDS TO BE CHANGED, THEN CHANGE DRAWING M.1 AS
 WELL.
  
 2- PROVIDE THE NAME AND SIGNATURE ON DRAWING M.1 OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. SUBMIT OLD COPIES
 (NOT STAPLED) FOR REFERENCE.
  