Date |
Text |
2015-11-20 10:50:23 | NOTE: ON 1/26/16 RECEIVED E-MAIL FROM ART LANGE. SEE |
| COPY BELOW. |
| |
| JULIO, |
| I SEE YOU HAVE COMPLETED THE PLAN REVIEW FOR THIS |
| PROPERTY. THE FRONT BUILDING IS IN BAD CONDITION. IT |
| HAS A NEW ROOF AND HOT WATER HEATER WITHOUT PERMITS. |
| THE INTERIOR HAS BEEN COMPLETELY DEMOLISHED AND ALL OF |
| THE EXTERIOR HAS BEEN REMOVED TO THE SHIP LAP. I SEE |
| THAT THERE IS MAJOR ROT THROUGH OUT AND MAY NEED SOME |
| STRUCTURAL REPAIRS TO THE FOUNDATION. |
| THERE IS A CURRENT STOP WORK ORDER FRO INTERIOR |
| EXTERIOR DEMO WITHOUT PERMITS. |
| THIS WILL REQUIRE A FULL SET OF PLANS INCLUDING |
| STRUCTURAL REPAIR DETAILS. EVERY TRADE PERMIT IS |
| REQUIRED. |
| REGARDS, |
| ART |
| |
| ART LANGE |
| BUILDING INSPECTOR |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES DEPARTMENT / BUILDING DIVISION |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33401 |
| 561-805-6667 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- SCOPE OF WORK SHOWN ON PLANS IS NOT CLEAR. PROVIDE A |
| COMPLETE DEMOLITION FLOOR PLAN SHOWING IN DETAILS THE |
| SCOPE OF DEMOLITION. AND, PROVIDE A SEPARATE AND |
| COMPLETE FLOOR PLAN SHOWING ALL THE PROPOSED SCOPE OF |
| WORK. SEC. 107.2.1 CITY AMENDMENTS. AND, PROVIDE |
| DIMENSIONS FOR ALL ROOMS ON THE PROPOSED FLOOR PLAN. |
| NOTE: SURVEY SUBMITTED SHOWS ONE STORY RESIDENCE UNDER |
| CONSTRUCTION. WAS THE HOUSE DEMOLISHED?. EXTERIOR |
| ELEVATIONS SHOW EXISTING ROOF SYSTEM TO REMAIN, BUT HOW |
| CAN A ROOF SYSTEM GOING TO REMAIN IF THE WALLS WERE |
| REMOVED?. PLEASE COORDINATE ALL THE INFORMATION ON |
| PLANS. |
| |
| 2- ACCORDING TO FLOOR JOIST LAYOUT ON SHEET S-1.0, THE |
| ENTIRE FLOOR FRAMING IS NEW. IT LOOKS LIKE THERE IS A |
| CRAWL SPACE BELOW FLOOR JOISTS. PROVIDE COMPLETE |
| INFORMATION SHOWING COMPLIANCE WITH SEC. R408 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE COMPLETE |
| DETAILS AND SPECIFICATIONS (SIZES, LOCATION, ETC) FOR: |
| VENTILATION, ACCESS TO THE CRAWL SPACE. ETC. |
| |
| 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. UPDATE THE VALUATION TO INCLUDE ALL THE |
| SCOPE OF WORK SHOWN ON THE REVISED PLANS AND ADD THE |
| DESIGN PROFESSIONAL FEES. |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) ALL WINDOWS AS SHOWN ON PLANS. |
| |
| B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY |
| IDENTIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE |
| CALCULATED DESIGN PRESSURES. |
| |
| C) EXTERIOR DOOR AS SHOWN ON PLANS. |
| |
| D) HURRICANE SHUTTERS IF WINDOWS AND DOOR WITH GLAZING |
| DON'T HAVE IMPACT GLASS. AND, PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. SEE CITY SAMPLE OF SHUTTERS |
| INSTALLATION SCHEDULE. OR PROVIDE A DIFFERENT |
| INSTALLATION SCHEDULE FORMAT THAT SHOWS ALL THE |
| REQUIRED INFORMATION SHOWN ON THE CITY SAMPLE. |
| |
| E) ROOF SHINGLES. (NO CLEAR IF PART OF THE SCOPE. SEE |
| ITEM #1 ABOVE). |
| |
| F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS. PROVIDE COPY OF THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL |
| NEXT TO EACH SPECIFIED CONNECTOR. |
| |
| 5- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 6- WINDOWS DESIGN PRESSURES SHOWN ON SHEET S-0.0 SEEM |
| TO BE LOW FOR A BUILDING LOCATED IN EXPOSURE "D" AS |
| STATED ON PLANS. PROVIDE CALCULATIONS SHOWING THE |
| CALCULATED DESIGN PRESSURES. SEC. 107.2.1.3 CITY |
| AMENDMENTS. |
| |
| 7- NEED TO SPECIFY SAFETY GLASS FOR WINDOW LOCATED IN |
| THE BATHROOM AND WINDOWS ADJACENT TO THE ENTRY DOOR. |
| SEC. R308.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 8- ENGINEER OF RECORD TO PROVIDE ALL HIS INFORMATION ON |
| THE TITLE BLOCK, INCLUDING THE ENGINEER'S ADDRESS AS |
| REQUIRED BY FAC 61G15-23.002. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE ANY REVISED DRAWING. SUBMIT OLD COPIES |
| (NOT STAPLED) FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |