2015-11-04 08:40:27 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | | FBC107 - PROVIDE ELECTRICAL PLAN. | | | | ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING, | | FIXED, MOBILE, OR PORTABLE, SHALL BE LISTED AND | | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS | | OTHERWISE APPROVED BY SPECIAL PERMISSION. NEC 600.3 | | LISTING. | | | | EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC | | 600.6(A)(1) | | | | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL | | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN | | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME | | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES | | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS | | OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4 | | | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|