2015-11-05 13:33:44 | CHRISTOPHER S. THROOP, C.B.O. |
| BLDG. PLANS EXAMINER ? PX3169 |
| (561) 805-6718 |
| [email protected] |
| |
| 1. THE STATED DESIGN WIND SPEED PRESSURES FROM YOUR |
| ROOF ZONE TABLE, PG. S-02 ARE LOW. PLEASE RE-CALCULATE |
| PNET AND RE-SUBMIT. |
| 2. PLEASE PROVIDE SIGNED AND SEALED REPORT FROM A |
| NATIONALLY RECOGNIZED TESTING LAB FOR THE TENSION TEST |
| RESULTS OF THE U-2000 ANCHOR SYSTEM. |
| 3. SPECIFY ATTACHMENT METHOD FOR THIS PROJECT. IF LAG |
| BOLTS ARE SELECTED, PLEASE PROVIDE ADDITIONAL |
| INFORMATION. I.E. SEALING OF ROOF MEMBRANE. |
| 4. REF. PG S-02, NOTES, LINE #8. PLEASE CHANGE |
| REFERENCED CODE TO FBC2014 5TH ED. |
| |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| 1703.5.1 TESTING. |
| AN APPROVED AGENCY SHALL TEST A REPRESENTATIVE SAMPLE |
| OF THE PRODUCT OR MATERIAL BEING LABELED TO THE |
| RELEVANT STANDARD OR STANDARDS. THE APPROVED AGENCY |
| SHALL MAINTAIN A RECORD OF THE TESTS PERFORMED. THE |
| RECORD SHALL PROVIDE SUFFICIENT DETAIL TO VERIFY |
| COMPLIANCE WITH THE TEST STANDARD. |
| |
| 1517.6.1 |
| METAL ACCESSORIES MAY BE OF A MANUFACTURED, |
| SHOP-FABRICATED OR FIELD-FABRICATED TYPE, PROVIDING THE |
| MATERIALS AND FASTENERS ARE IN COMPLIANCE WITH THE |
| MINIMUM REQUIREMENTS OF THIS CODE AND SHALL BE SIZED, |
| DESIGNED AND INSTALLED IN COMPLIANCE WITH METHODS SET |
| FORTH IN RAS 111. |
| |
| 1ST REVIEW: FBC 2014 5TH ED. |