 1. THE STATED DESIGN WIND SPEED PRESSURES FROM YOUR
 ROOF ZONE TABLE, PG. S-02 ARE LOW. PLEASE RE-CALCULATE
 PNET AND RE-SUBMIT.
 2. PLEASE PROVIDE SIGNED AND SEALED REPORT FROM A
 NATIONALLY RECOGNIZED TESTING LAB FOR THE TENSION TEST
 RESULTS OF THE U-2000 ANCHOR SYSTEM.
 3. SPECIFY ATTACHMENT METHOD FOR THIS PROJECT. IF LAG
 BOLTS ARE SELECTED, PLEASE PROVIDE ADDITIONAL
 INFORMATION. I.E. SEALING OF ROOF MEMBRANE.
 4. REF. PG S-02, NOTES, LINE #8. PLEASE CHANGE
 REFERENCED CODE TO FBC2014 5TH ED.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 1703.5.1 TESTING.
 AN APPROVED AGENCY SHALL TEST A REPRESENTATIVE SAMPLE
 OF THE PRODUCT OR MATERIAL BEING LABELED TO THE
 RELEVANT STANDARD OR STANDARDS. THE APPROVED AGENCY
 SHALL MAINTAIN A RECORD OF THE TESTS PERFORMED. THE
 RECORD SHALL PROVIDE SUFFICIENT DETAIL TO VERIFY
 COMPLIANCE WITH THE TEST STANDARD.
  
 1517.6.1
 METAL ACCESSORIES MAY BE OF A MANUFACTURED,
 SHOP-FABRICATED OR FIELD-FABRICATED TYPE, PROVIDING THE
 MATERIALS AND FASTENERS ARE IN COMPLIANCE WITH THE
 MINIMUM REQUIREMENTS OF THIS CODE AND SHALL BE SIZED,
 DESIGNED AND INSTALLED IN COMPLIANCE WITH METHODS SET
 FORTH IN RAS 111.
  
 1ST REVIEW: FBC 2014 5TH ED.