2016-03-23 19:43:04PASSED ELECTRICAL REVIEW BUT MADE SEVERAL NOTES ON THE
 PLANS FOR FINAL INSPECTIONS.
 1. REVISED THE QUOTED EDITION OF THE NEC TO 2011
 2. MARKED FACP CKT ON BOTH PANEL SCHEDULE AND FIRE
 ALARM RISER TO REFERENCE NEC 760.121 (B) INDICATING THE
 BRANCH CIRCUIT REQUIREMENTS.
 3. MARKED THE PANEL SCHEDULE TO NOTE THAT THE EWC SHALL
 BE PROTECTED BY GFCI AS PER NEC 422.52
  
  