Plan Review Notes
Plan Review Notes For Permit 15100606
Permit Number 15100606
Review Stop M
Sequence Number 1
Notes
Date Text
2015-11-03 15:34:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #1510606
 11/3/15
  
 1) SHEET A1.1: PROVIDE THE LEVEL OF ALTERATION FOR THE
 PROPOSED PROJECT IN COMPLIANCE WITH SECTION 501.1
 FBC-14 EXISTING BUILDING
 2) M-1.1: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING: ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62. PROVIDE CALCULATIONS ON THE
 PLAN VERIFYING COMPLIANCE.
 3) M-1.1: PROVIDE DUCT SIZES ON THE PLANS, AND HANGING
 AND SUPPORT DETAILS IN COMPLIANCE WITH THE CURRENT
 SMACNA STANDARDS.
 4) PROVIDE AN AIR DEVICE SCHEDULE FOR THE DIFFUSERS AND
 RETURN GRILLS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  