Plan Review Notes For Permit 15100606 |
Permit Number |
15100606 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-11-03 15:34:42 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #1510606 | | 11/3/15 | | | | 1) SHEET A1.1: PROVIDE THE LEVEL OF ALTERATION FOR THE | | PROPOSED PROJECT IN COMPLIANCE WITH SECTION 501.1 | | FBC-14 EXISTING BUILDING | | 2) M-1.1: REFER TO SECTION 809.2 FBC-14 EXISTING | | BUILDING: ALTERED EXISTING SYSTEMS. | | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | PROCEDURE OF ASHRAE 62. PROVIDE CALCULATIONS ON THE | | PLAN VERIFYING COMPLIANCE. | | 3) M-1.1: PROVIDE DUCT SIZES ON THE PLANS, AND HANGING | | AND SUPPORT DETAILS IN COMPLIANCE WITH THE CURRENT | | SMACNA STANDARDS. | | 4) PROVIDE AN AIR DEVICE SCHEDULE FOR THE DIFFUSERS AND | | RETURN GRILLS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|