2015-11-19 13:01:08 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| FIRE ALARM WORK SHALL BE ON A SEPARATE PERMIT AND SHOP |
| DRAWINGS. |
| 1. YOU HAVE A MYRIAD OF CODES REFERENCED ON THE PLANS. |
| REVISE YOU PLANS TO REFLECT ONLY THE APPLICABLE CODES |
| AND LET THEM BE CONSISTENT THROUGHOUT THE PLANS. |
| 2. FBC-E SECTION C402.4.8 REQUIRES THAT ALL RECESSED |
| LIGHTING INSTALLED IN THE BUILDING?S THERMAL ENVELOPE |
| BE IC RATED AND SEALED TO LIMIT THE LEAKAGE OF AIR |
| BETWEEN CONDITIONED AND NONCONDITIONED SPACE. |
| 3. NEC 700.12 REQUIRES THAT ALL EMERGENCY LIGHTS AND |
| EXIT LIGHTS BE ON THE LIGHTING CIRCUIT FOR THE AREA |
| WHICH THEY OCCUPY. |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |