2015-11-03 18:26:15 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND |
| BELOW ARE THE DEFICIENCIES NOTED. |
| 1. FBC-ENERGY CONSERVATION CODE SECTION 402.4.8 |
| RECESSED LIGHTING STATES THAT ALL RECESSED LIGHTING |
| INSTALLED IN THE BLDG.?S THERMAL ENVELOPE SHALL BE |
| EITHER IC RATED OR SEALED TO PREVENT AIR LEAKAGE |
| BETWEEN CONDITIONED AND NON-CONDITIONED SPACES. |
| 2. NEC 215.5 DIAGRAMS OF FEEDERS, A SITE SPECIFIC |
| FEEDER DIAGRAM SHALL BE PROVIDED. THIS DIAGRAM SHALL |
| INCLUDE LOAD CALCS AND CONDUCTOR SIZING SPECIFICALLY |
| FOR THE PANEL OF THE AREAS COVERED WITHIN THE SCOPE OF |
| THIS PERMIT. |
| 3. NEC 220.16 REQUIRES THAT LOAD CALCS BE PROVIDED TO |
| ASCERTAIN THAT THE EXISTING SERVICE CAN ABSORB THE |
| ADDED LOAD. |
| 4. THERE ARE SEVERAL ROOMS WITHOUT WINDOWS WHICH MAY |
| REQUIRE ADDITIONAL EMERGENCY LIGHTING. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| |