Plan Review Notes
Plan Review Notes For Permit 15100572
Permit Number 15100572
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-03 18:26:15THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND
 BELOW ARE THE DEFICIENCIES NOTED.
 1. FBC-ENERGY CONSERVATION CODE SECTION 402.4.8
 RECESSED LIGHTING STATES THAT ALL RECESSED LIGHTING
 INSTALLED IN THE BLDG.?S THERMAL ENVELOPE SHALL BE
 EITHER IC RATED OR SEALED TO PREVENT AIR LEAKAGE
 BETWEEN CONDITIONED AND NON-CONDITIONED SPACES.
 2. NEC 215.5 DIAGRAMS OF FEEDERS, A SITE SPECIFIC
 FEEDER DIAGRAM SHALL BE PROVIDED. THIS DIAGRAM SHALL
 INCLUDE LOAD CALCS AND CONDUCTOR SIZING SPECIFICALLY
 FOR THE PANEL OF THE AREAS COVERED WITHIN THE SCOPE OF
 THIS PERMIT.
 3. NEC 220.16 REQUIRES THAT LOAD CALCS BE PROVIDED TO
 ASCERTAIN THAT THE EXISTING SERVICE CAN ABSORB THE
 ADDED LOAD.
 4. THERE ARE SEVERAL ROOMS WITHOUT WINDOWS WHICH MAY
 REQUIRE ADDITIONAL EMERGENCY LIGHTING.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  