2015-11-30 15:20:132ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHEET M1.1 SHOWS CWS/R LINES TO WATER SOURCE HEAT
 PUMP DETAIL #5 ON M5.1 DOES NOT SHOW THE 1/2 IN POTABLE
 WATER CONNECTION THAT IS SHOWN ON PLUMBING PLAN PLEASE
 CLARIFY.
 PER WPB AMEND. TO FBC SEC 107.2.1
 2.ON THE PLUMBING PLAN IT SHOWS A AIR HANDLER AND
 ON THE MECHANICAL IT SHOWS WATER SOURCE HEAT PUMP
 PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC 107.2.1
 3. PLEASE CLARIFY USE OF 1/2IN POTABLE WATER LINE
 CONNECTED TO AIR HANDLER.
 PER WPB AMEND. TO FBC SEC 107.2.1
 4.PLEASE SPECIFY TYPE OF BACK FLOW ON PLAN AIR GAP OR
 RPZ REQUIRED.
 PER WPB AMEND. TO FBC SEC 107.2.1