Plan Review Notes For Permit 15100544 |
Permit Number |
15100544 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-22 16:44:56 | | | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | | | 1.FLOOR DRAIN WAS ELIMANATED ON JOB PLEASE RMOVE FROM | | SHEETS P0.1,P0.2. | | 2. BACKFLOW REQUIRED ON CW LINE CONNECTED TO AIR | | HANDLER. PER FBCP SEC 608.3 DEVICES, APPURTENANCES, | | APPLIANCES AND APPARATUS. | | DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS | | INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS | | STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR | | STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER | | SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION | | AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY | | SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS AND | | OTHER APPLIANCES AND DEVICES THAT HANDLE OR TREAT | | POTABLE WATER SHALL BE PROTECTED AGAINST CONTAMINATION. |
|