Plan Review Notes For Permit 15100514 |
Permit Number |
15100514 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-16 10:54:01 | | | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: | | | | 1.SHOW EXISYTING GAS . SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE AND | | CORRESPONDING LENGTHS PER FBC-2014 FUEL GAS, SECS. | | 402.4.1, 402.4.2. | | 2.INDICATE TYPE OF COATING YOU ARE USING PER FBC FG | | 2014 SEC 404.11 PROTECTION AGAINST CORROSION. | | METALLIC PIPE OR TUBING EXPOSED TO CORROSIVE ACTION, | | SUCH AS SOIL CONDITION OR MOISTURE, SHALL BE PROTECTED | | IN AN APPROVED MANNER. ZINC COATINGS (GALVANIZING) | | SHALL NOT BE DEEMED ADEQUATE PROTECTION FOR GAS PIPING | | UNDERGROUND. WHERE DISSIMILAR METALS ARE JOINED | | UNDERGROUND, AN INSULATING COUPLING OR FITTING SHALL BE | | USED. PIPING SHALL NOT BE LAID IN CONTACT WITH CINDERS | | 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
|