Plan Review Notes
Plan Review Notes For Permit 15100503
Permit Number 15100503
Review Stop E
Sequence Number 2
Notes
Date Text
2016-03-17 10:56:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - CKT # 21 SHOWS A 15 AMP OCPD FOR A BATHROOM GFCI NEC
 210.12 C3 STATES A MINIMUM 20 AMPERE BRANCH CIRCUIT.
  
 - KITCHEN ISLAND IS MISSING RECEPTACLES AT EACH END OF
 THE COUNTER WITHIN 12" OF THE TOP. NEC 210.52 C2 ( GFCI
 PROTECTION REQUIRED )
  
 - NEW RECCESSED LIGHTING MUST COMPLY WITH 75 % HIGH
 EFFIENCY AS WELL AS IC RATED /SEALED (2CFM) AS NOT TO
 COMPROMISE THERMAL ENVELOPE. FBC-ER 404.1.1 & 402.4.4