Plan Review Notes For Permit 15100503 |
Permit Number |
15100503 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-03-17 10:56:12 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - CKT # 21 SHOWS A 15 AMP OCPD FOR A BATHROOM GFCI NEC | | 210.12 C3 STATES A MINIMUM 20 AMPERE BRANCH CIRCUIT. | | | | - KITCHEN ISLAND IS MISSING RECEPTACLES AT EACH END OF | | THE COUNTER WITHIN 12" OF THE TOP. NEC 210.52 C2 ( GFCI | | PROTECTION REQUIRED ) | | | | - NEW RECCESSED LIGHTING MUST COMPLY WITH 75 % HIGH | | EFFIENCY AS WELL AS IC RATED /SEALED (2CFM) AS NOT TO | | COMPROMISE THERMAL ENVELOPE. FBC-ER 404.1.1 & 402.4.4 |
|