Plan Review Notes
Plan Review Notes For Permit 15100410
Permit Number 15100410
Review Stop B
Sequence Number 1
Notes
Date Text
2015-10-15 07:31:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100410
 ADD: 310 S. DIXIE HWY.
 CONT: KAST
 TEL: (561)603-9031
 E-MAIL:MSDH@ KASTBUILD.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. OCT. 15/2015
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS. SHEET S-1 SHOWS (3) DETAILS OF
 HOW THE AHELICAL PIER ARE TO BE INSTALLED. THE MAJORITY
 OF THE WALL IS SHOWN WITH A PIER TYPE 2, WHERE THE
 RIGHT SIDE OF THE PLAN ALSO SHOWS A PIER TYPE 2
 INSTALATION. THE MAJORITY OF THE WALL SHOULD BE SHOWN
 AS A PIER TYPE 1 AS DETICTED IN THE DETAIL. DISCREPANCY
 IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  